Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
5 - 10 Installation
Issue 8 January 1999
AC Power Cables
Use Figures 5-3 and 5-4 as references for this section. Observe
all precautions in Section 4.
1. Disconnect ac power from ac distribution service panel
that supplies power to the rectifier.
2. Install three fuse holders (one for each phase) or one
circuit breaker for the rectifier in the ac service panel.
Leave circuit breaker in off position or leave fuses out.
3. Install three phase leads and ac ground (AC EG) at service
panel and route conductors to rectifier.
4. Install crimp connectors onto phase leads and AC EG lead
as required by plant installation. Use the proper crimping
tool and die for the connector to prevent damage to
equipment. (See Table 5-A.)
5. Secure phase leads and AC EG lead in rectifier. Install
ground lead first. Torque phase connections to 3 Nm or 30
inch-pounds (in-lb). Torque AC EG connection to 4 Nm
(30 in-lb).
6. Verify that the branch circuit breaker to the rectifier in the
ac service panel is off or fuses are removed. Reenergize ac
service panel. Tag branch circuit breaker or fuse holders to
inform others not to close (turn on) the breaker or insert
fuses. If the branch circuit is protected by fuses, physically
remove the fuses from the area of the ac distribution
service panel.
DC Power Cables
Plant bus bars carry up to 52 volts dc. Observe DANGER
warnings in Section 4. Use Figures 5-3 and 5-4 as references for
this section.
1. Turn circuit breaker, CB1 on the rectifier, off (down).
2. Measure the lengths of cable required to run the dc output
cable from the rectifier to its termination point on the
charge bus, and to run the dc return cable from the rectifier
to its termination point on the charge ground bus.
3. Cut cables to length and install crimp connectors. Use the
proper crimping tool and die for the connector to prevent
damage to equipment. See Table 5-C.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...