Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Testing 6 - 11
Control (TR) Test
1. Press and hold the transfer rectifier (TR) switch on the test
set for 5 seconds. The rectifier should turn off simulating a
remote shutdown from the controller. The TRH lamp on
the test set should light.
2. Release the switch. The rectifier should restart and the
TRH lamp should go out.
3. Reduce the test load to 0 amperes.
4. Press the HV switch on the test set. The rectifier should
continue to operate.
Selective High
Voltage
Shutdown
(SHVSD) and
Restart
1. Adjust the test load so that the rectifier delivers 20 to 30A,
10 to 15 percent of its rated amperage.
2. Momentarily press the HV switch on the test set. The
rectifier should shut down, and the RFA LEDs on the
control panel and on the test set should light.
3. Momentarily press the RS switch on the test set. The
rectifier should restart and both RFA lamps should go off.
Float/Equalize
Test
1. Adjust the load so that the rectifier delivers between 20
and 30 amperes.
2. Turn the Power switch Off.
3. Short TB2 terminals EQL and EQLR on CM4.
4. Turn the Power switch On. The equalize LED should
light.
5. Use the Equal Adj potentiometer on the control panel to
set the voltage per the plant requirement, normally 2.0
(1.0) volts above float voltage.
6. Turn the Power switch Off.
7. Remove strap from TB2 on CM4 or return it to original
setting.
8. Turn the Power switch On.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...