Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Troubleshooting and Adjustments 7 - 7
Power switch off
Rectifier turned off manually
Power switch off or On
Power LED off
Output meter on
Rectifier operating normally;
S2.2 of CM4 has been enabled.
Power switch off or On (Enabled)
Power LED off
LCA LED On
Load share feature is not
operating properly
ACF LED On
All other conditions “don’t care”
AC input to rectifier fails on all
three phases
Power switch on On or Auto (Standard)
Power LED On (Standard)
Rectifier operating normally except not
load sharing
LSF LED On
Load share interconnect bus has
a short circuit.
Load share bus has opened, but
rectifier is otherwise normal.
Notes
S2.2 on CM4 permits the meter to be On or Off with the rectifier turned
Off.
S1 of CM4 must be in “Remote/Auto Control” position if the Power
switch is in the Auto position.
Table 7-B: Front Panel Conditions and Indications
Condition
Indication