Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
7 - 2 Troubleshooting and Adjustments
Issue 8 January 1999
the cable tie anchors to permit its withdrawal through the
conductor opening in the cabinet. The cable tie anchors,
while providing a secure physical support of the cable
assembly, protect the cable assembly from undesirable
abrasion and bending.
When a Lucent controller is not used, disconnect the
remote bay cable assembly from the rectifier at terminal
strips TB1 and TB2 of interface board CM4.
5. The rectifier's output filter capacitor must be completely
discharged. Verify by connecting a DMM directly to the
capacitor bus bars inside the rectifier. It will take a few
minutes to completely discharge the capacitors, after the
CB1 circuit breaker is turned off in Step (1).
6. One at a time, disconnect the battery plant end of the dc
output and output return conductors from the battery plant
charge and charge ground bus bars. Insulate the connector
ends and label the conductors for easy identification when
reconnecting.
7. One at a time, disconnect the dc output conductors from
the rectifier “hot” and return bus bars. Insulate the
connector ends and label the conductors for easy
identification when reconnecting.
8. One at a time, disconnect the ac input conductors from
their terminations, the ac equipment ground (green)
conductor from the AC EG/FR GRD in the cabinet, and
the central office (CO) ground interconnecting the top of
the rectifiers. Insulate the connector ends and label the
conductors for easy identification when reconnecting.
9. Unfasten the ac conduit that is structurally attached to the
rectifier. Place the disconnected conduit to the side, and, if
necessary, tie the conduit to an adjacent structure to
prevent interference with the rectifier removal.
10. Withdraw all disconnected conductors from the rectifier
cabinet and place them aside so as not to interfere with the
rectifier removal or cause a personnel hazard.
11. If provided, remove the straps fastening adjacent cabinets
together on the top surface.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...