Issue 8 January 1999
Local Equalize
Control Test
1. Set switch S2.1 on CM4 to on (right).
2. Move the FLT/EQ switch on the control panel (S2 on
CM3) to the equalize position. The equalize LED should
light.
3. Disable the local equalize feature, if necessary, by setting
the S2.1 switch on CM4 to off (left).
4. Return the FLT/EQ switch to the float position.
Low Current
Alarm (LCA)
Test (48V only)
1. If using the load share option, verify that the S1.9 switch
on CM2 is in the 1 position (on).
2. Reduce the load to 0 amperes.
3. The LCA LED on the front panel should light and the
LCA alarm should issue to TB3, terminals 5 and 6.
Load Share Fail
(LSF) Test (48V
only)
1. Holding the insulation on a piece of wire, insert the wire in
FS1 on CM2.
2. The LSF LED on the control panel should light and the
LSF alarm should be generated on TB3-9 and TB3-10 of
CM4.
Meter Test
1. Adjust the load so that the rectifier delivers approximately
100 amperes, 50% of its rated current capacity.
2. Connect a DMM, set on the dc millivolt scale, across the
329 test points E25/E26. See Figure 6-2.
3. Observe the DMM and record the rectifier’s shunt voltage.
The shunt is rated 250A/50mV = 5A/mV, which means
that each millivolt of voltage drop across the shunt
indicates 5A of output current.
4. Convert the DMM shunt voltage reading to amperes. For
example, if the DMM reads 20mV, then 20mV x 5A/mV =
100A of output current.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...