Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Replacing Components and Circuit Modules 8 - 15
4. At the plant controller, remove the fuse REG fuse
associated with the rectifier.
5. At the rectifier, loosen the locking screws and open the
door.
Caution
Support the CM7 control board with your hands when
connecting and disconnecting the cables, or damage to the board
may result. DO NOT disconnect cables by pulling the cable.
6. Disconnect control cable connector J5A from the CM4
board by unlatching first, then pulling the connector.
7. Disconnect the connecting cables from CM7.
8. Remove CM7 from any support standoffs by using a small
flat-bladed screwdriver to push in the latches on each
standoff. Remove the two screws holding CM7 in place.
9. Position the new CM7 board over the two screw standoffs.
Verify that each latch snaps and locks in place. Restore the
two screws.
10. Reconnect connecting cables to CM7.
11. If the rectifier is to be restored to service, refer to Section
7, “Restore Rectifier to Service.”
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...