5 - 14 Installation
Issue 8 January 1999
8. Dress and tie down the cable to provide stress relief at the
connector.
9. This step is not necessary if a Galaxy controller is used
with the H285-226 L60 enhanced signals control cable. If
-48 volt rectifiers are to be operated in load share, connect
a 20 gauge wire from TB3-7 on CM4 to TB3-8 on CM4 of
the adjacent rectifier. See Figure 5-6. The wire must be UL
recognized with minimum ratings of 80° C and 150 volts
ac. All load-sharing rectifiers must be “daisy-chain”
connected in this manner.
In addition to the signals provided when a Lucent
controller is used, 34 signals are readily accessible on the
CM4 interface board via terminal strips TB1, TB2, and
Figure 5-6: CM4 Interface Board (330C)
Connector for
Plant Control
Cable
Connections for
Special
Applications
Load Share
Voltage
Adjustment
Potentiometer
for Special
Applications
Load Share