Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Installation 5 - 9
7. Remove parts package from inside rectifier.
8. Verify that the main ac voltage at your distribution panel
agrees with the input specified on the label inside the
rectifier door.
9. Using all four lifting eyebolts and appropriate material
handling equipment, raise the rectifier from the pallet and
set it on the floor in its upright vertical position.
Installing or
Adding a
Rectifier
This procedure is appropriate for installing a rectifier in a new
plant or adding a rectifier to an existing plant to increase
capacity. The assumption here is that the rectifier is being added
to an operating plant.
Observe the safety precautions in Section 4 and those within
each procedure whenever working on or near electrically live
equipment. Only persons trained and experienced in the
installation of power equipment should install this rectifier.
Locate and
Anchor the
Rectifier
1. Using site drawing information, locate the exact position
specified for the rectifier.
DANGER
Wear eye protection devices when drilling holes for floor
anchors.
2. Using template found in service kit provided with each
rectifier, drill holes for a minimum of two diagonally
placed floor anchors. (In Earthquake Zone 3 or 4, drill all
four holes.)
3. Set anchors and, if on raised floor, assemble tie down rods
and couplings.
4. Using appropriate material handling equipment, move the
rectifier into place, level, shim if necessary, and anchor
with bolts and washers. Torque to 81 Newton-meters (Nm)
or 60 foot-pounds (ft-lb). Torque bolts from kit H569-407
Group 1 to 30 Newton-meters (Nm) or 22 foot-pounds
(ft-lb).
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...