Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
8 - 14 Replacing Components and Circuit Modules
Issue 8 January 1999
5. At the rectifier, loosen the locking screws and open the
door.
Caution
Support the CM4 control board with your hands when
connecting and disconnecting the cables, or damage to the board
may result. DO NOT disconnect cables by pulling the cable.
6. Disconnect control cable connector J5A from the CM4
board by unlatching first, then pulling the connector.
7. Disconnect the connecting cables from CM4.
8. Remove CM4 from the support standoffs by using a small
flat-bladed screwdriver to push in the latches on each
standoff.
9. Position the new CM4 board over the standoffs. Verify
that each latch snaps and locks in place.
10. Reconnect connecting cables to CM4.
11. If the rectifier is to be restored to service, refer to Section
7, “Restore Rectifier to Service.”
CM5 or CM6
Snubber Board
1. Remove the quick-disconnect connectors from the board.
2. Push in on the plastic locking tabs to free the board.
3. Remove any screws holding the board in place.
4. Reinstall in reverse order.
CM7
Transformer
Board
Minimize electrostatic discharge when handling circuit
modules. Observe all warnings in Section 4, Safety.
1. Turn the rectifier Power switch Off.
2. Turn the rectifier CB1 circuit breaker Off (down).
3. At the ac service panel supplying power to the rectifier,
remove the input fuses assigned to the rectifier, or turn the
circuit breaker Off.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...