background image

ENERGY STOR AGE INVERTERS 

PQstorI

Installation, operation and 
maintenance instructions

Содержание PQstorI

Страница 1: ...ENERGY STOR AGE INVERTERS PQstorI Installation operation and maintenance instructions...

Страница 2: ...5 User settings 3 6 Installation settings 3 7 Monitoring 3 8 System settings 3 9 Modbus commands 04 Installation 4 1 Upon reception 4 2 Location 4 3 Identification tag 4 4 Mechanical installation 4 5...

Страница 3: ...easurements 6 3 Checking system faults 6 3 Retrieving manufacturer data 07 Maintenance 7 1 Maintenance intervals 7 2 Check system faults and operating hours 7 3 Cleaning and tightening screws 7 4 Repl...

Страница 4: ...lternating current voltage AC 4 5 2 Direct current voltage DC 4 5 3 Grounding 4 5 1 Phase connection 4 5 2 DANGER These safety instructions are intended for all work on the PQstorI range of products N...

Страница 5: ...urement of the AC voltage across 1 pole of the islanding contactor breaker not functional at present Section 4 5 4 Output to control the islanding contactor breaker Section 4 5 4 Input for the 24Vdc s...

Страница 6: ...strating the internal components of the PQstorI product Figure 3 Block diagram of main PQstorI components E L1 DC DC L2 L3 N1 N2 24V EXT 24V INT 24 V DC FUSES DC RELAYS DC BUS POWER MODULE LCL FILTER...

Страница 7: ...Green LED on and steady Module is on or starting up Red LED blinking Module has encountered a critical error Green and red steady Firmware is updating Yellow LED blinking Wi Fi traffic 2 4 LEDs The g...

Страница 8: ...through the Wi Fi user interface click the Edit button at the bottom of a settings page in Figure 5 input your changes in the Value column of the settings table in Figure 6 and click the Save button i...

Страница 9: ...l component of all line currents 3 4 3 AIP Irms L1 3 RMS value of the 3 phase inverter current 3 4 4 AIP Irms N RMS value of the neutral inverter current 4 wire mode P Active power on the network at t...

Страница 10: ...a similar way to the table for the voltage spectrum 3 4 4 Device Currents AIP Irms L1 3 reports the RMS value of the current injected into each phase line of the network and AIP Irms N reports the cu...

Страница 11: ...wer is the rated module power Even when operating multiple modules in parallel enter the rating for a single module i e 30 kW for smaller PQstorI units 3 6 3 CT Settings PQstorI can measure the line c...

Страница 12: ...of the PQstorI only operation on grid connected is available so that will be status shown in the AIP Monitoring window Battery Voltage is the DC voltage across the battery ter minals and Battery Curr...

Страница 13: ...uld not be preloaded The voltage increase on the DC capacitors during the preload phase is not high enough Inverter trips reset required DC Top over voltage The DC over voltage protection of the capac...

Страница 14: ...ps reset required DSP timeout DSP didn t give any feedback within 2 seconds after a start stop request command was sent to it Inverter trips reset required Heart beat timeout AIP has stopped upon rece...

Страница 15: ...dministrators to set the Hostname Realm IP Address and Network Mask of the Wi Fi network emitted by the module to connect to the user interface Set the Wi Fi mode to Access Point to connect directly t...

Страница 16: ...Float 2 0 3200 The rms voltage measured between the phases L2 and L3 L2 and Neutral when connected in 4 wire mode VrmsL3L1 30505 V Float 2 0 3200 The rms voltage measured between the phases L3 and L1...

Страница 17: ...tDSPError for the list of possible DSP errors Islanding Status 36201 Dword 2 0 2 When set 1 means that unit is in Islanding mode when cleared 0 it is in grid connected mode Available in the future Bla...

Страница 18: ...positive when discharging the battery Udc Inverter DC voltage 30523 V Float 2 0 3200 The DC voltage present on the inverter DC bus Name Address Unit Type Register length Range Description Min Max Star...

Страница 19: ...ion Make sure that you transport store and operate the product within the range of temperature a Up to 50 C 122 F with auto derating b Locations with normal levels of contaminants experienced in urban...

Страница 20: ...used for the power cabling of the inverter The maximum cable size that can fit into these terminals is 25 mm2 The wiring methods for electrical installation of the inverter shall be in accordance wit...

Страница 21: ...k start islanding functions not available yet The black start board includes supercaps to enable the inverter to ride through low voltage interruptions while still providing energy for the control cir...

Страница 22: ...e operating conditions of the PQstorI require class 1 0 X 5A CT that can withstand 15 VA over 20 meters of 2 5 mm2 14AWG cables Insert each CT wire into the appropriate pole of the spring contact fema...

Страница 23: ...it is not mechanically or electrically damaged and that it can tolerate the voltage on the electrical network Close the upstream protection for powering the module If the cabling is correct the red s...

Страница 24: ...ry addi tional 1 C 1 8 F Maximum allowed ambient temperature is 50 C 122 F Failing to derate the system risks leading to malfunction and could damage the equipment Navigate to the Derating page Sectio...

Страница 25: ...ty to provide and continuously ensure a secure connection between the product and user network or any other network as the case may be User shall establish and maintain any appropriate measures such a...

Страница 26: ...current and voltage on each line on the electrical network navigate to the Voltages and Line Current pages of the Wi Fi user interface as described in Sections 3 4 2 and 3 4 3 respectively 6 3 Checkin...

Страница 27: ...nths 7 3 Change cooling fan 40 000 hours of operation 7 4 07 Maintenance 7 2 Check system faults and operating hours Navigate to the page on Event Logging of the Wi Fi user interface to check for rece...

Страница 28: ...if it has been damaged if the system is overheating or after 40 000 hours of operation You can order fan replacement kits from your ABB supplier To replace the fan Unscrew the three screws on the fron...

Страница 29: ...condensing during operation Max 85 non condensing during storage Pollution Degree PD2 Overvoltage Category OVC III AC OVC II DC Altitude Indoor installation in clean environment at 1000m upto 5000m w...

Страница 30: ...ly open 5 A 30 VDC Mechanical aspects Mounting Modules suitable to integrate into a cabinet on draws or as part of a rack system with push connectors Wall mounted Dimensions W x D x H 435 x 459 x 130...

Страница 31: ...cle code a Module 1 M Software version b Wi Fi user interface controller software DSP software Installation location 9 1 Module identification Remarks a Read from main identification tag located on th...

Страница 32: ...eck the setting and operation of the protective apparatus Check tightness of conductor fixations The material of terminals and conductors must be compatible corrosion Installation a Check the voltage...

Страница 33: ...le terminal Input 1 is connected to the CT including sign a Line 1 2 3 1 2 3 Module terminal Input 2 is connected to the CT including sign a Line 1 2 3 1 2 3 Module terminal Input 3 is connected to th...

Страница 34: ...the current of the inverter Check the power absorbed by the inverter Check the batteries voltage through the BMS Check the batteries current through the BMS Set the P setpoint to 0 Set up the user req...

Страница 35: ...warn Prog alarm 2 T crtl warn Prog alarm 3 V min warn Alarm delay V max warn Alarm rst del Imbalance Ground fault Start Stop Settings Prog Warnings Stdby status Prog warn 1 Standby level Prog warn 2 S...

Страница 36: ...ument without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in...