Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
6 - 8 Testing
Issue 8 January 1999
Testing Off
Line
The following tests involve use of the test load and a Battery
Plant Simulator Test Set. Refer to page 6-2 for the procedure to
connect a test load and pages 6-2 and 6-3 for a Battery Plant
Simulator Test Set.
If the rectifier fails any of the tests in this section, replace the
CM2 board and begin testing again.
Startup
1. Turn on the ac supply to the rectifier. The PWR lamp on
the test set should light brightly. If it does not light
properly, check the connection of the two small red and
black clip leads. They may be reversed or otherwise
incorrectly connected. These leads provide the operating
voltages in the test set, and the red lead should be
approxi27 volts dc with respect to the black lead.
2. The PWR lamp should remain lit during the remaining
tests as long as the ac supply is turned on.
3. Set the test meter to the 100 volts range, and connect it to
the Rect jacks on the rectifier control panel. (See Figure
2-2.)
4. Adjust the test load so that when the rectifier is turned on,
it will deliver 10-40A, 5 to 20 percent of full load.
5. Place the S1 switch on CM4 in the LOC position (see
Figure 5-5), and turn the Power switch On. The rectifier
should start and the green Power LED on the front panel
should light. The test meter should indicate 40-50 or 22-26
volts. The MAN lamp on the test set should light and
remain lit as long as the rectifier is turned on.
Regulation
(NL/FL) Test
1. Watch the test meter and move the Rect Test switch to
NL. In the NL position, the voltage should drop between
0.3 and 0.6 volt.
2. Repeat Step 1 with the Rect Test switch in the FL position.
The voltage should increase between 0.1 and 0.4 volt.
Rectifier Failure
Alarm Test
1. Holding the insulation on a piece of bare wire or the end of
a paper clip, insert the wire into the fuse holder of the F1
alarm fuse on CM1. Note that the rectifier shuts down, and
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...