5 SETPOINTS
5.6 S4 ELEMENTS
5
c) HARMONIC DERATING
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
HARMONICS
ÖØ
W1(3) HARM DERATING
•
MINIMUM OPERATING CURRENT
: Enter the minimum value of current (in units of relay nominal current) required to
allow the Harmonic Derating element to operate.
•
W1(3) HARMONIC DERATING PICKUP
: Enter the harmonic derating below which the Winding 1(3) Harmonic Derat-
ing will pickup and start the delay timer.
•
W1(3) HARMONIC DERATING DELAY
: Enter the time that the harmonic derating must remain below the pickup level
before the element operates.
Figure 5–35: HARMONIC DERATING SCHEME LOGIC
W1 HARM DERATING
[ENTER] for more
W1 HARM DERATING
FUNCTION: Disabled
Range: Enabled, Disabled
W1 HARM DERATING
TARGET: Self-Reset
Range: Self-Reset, Latched, None
MINIMUM OPERATING
CURRENT: 0.10 x CT
Range: 0.03 to 1.00 x CT in steps of 0.01
W1 HARM DERATING
PICKUP: 0.90
Range: 0.01 to 0.98 in steps of 0.01
W1 HARM DERATING
DELAY: 10 s
Range: 0 to 60000 s in steps of 1
W1 HARM DERATING
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled