GE Multilin
745 Transformer Management Relay
2-5
2 GETTING STARTED
2.2 SECURITY
2
2.2SECURITY
2.2.1 INSTALLATION
Note that the relay is defaulted to the
Setpoints Not Programmed
state before it leaves the factory. This safeguards against
the installation of a relay whose setpoints have not been entered. In addition, a relay in the
Not Programmed
state blocks
signaling of any output relay, and turns off the In Service LED indicator.
Move to the
S1 745 SETUP
ÖØ
INSTALLATION
ÖØ
745 SETPOINTS
message. To put the relay in the
Programmed
state, press
the
or
key once and press
. Enter Yes for the
ARE YOU SURE?
message. The In Service LED
indicator will now turn on.
2.2.2 CHANGING THE PASSCODE
To guarantee that the relay settings cannot be tampered with, the user may setup the passcode security feature.
1.
Move to the
S1 745 SETUP
Ö
PASSCODE
Ö
SETPOINT ACCESS
message. This message cannot be edited directly. It sim-
ply indicates whether passcode security is enabled (
SETPOINT ACCESS:
“Read Only”), or passcode security is disabled
(
SETPOINT ACCESS:
“Read & Write”). Each relay is shipped from the factory with setpoint access allowed. The pass-
code is also defaulted to '0', which disables the passcode security feature entirely.
2.
Press the
key once.
3.
Press the
or
key once.
4.
Press the
key to begin the procedure of changing the passcode. The displayed message will change as shown.
The current passcode is '0', so press the '0' numeric key. The relay will acknowledge the key press by displaying 'z‘.
5.
Press the
key.
6.
For this example, change the passcode to “123” by pressing the appropriate numeric keys in the
1 2 3
sequence. The
message will change as the digits are entered, with the end result being as shown.
7.
Press the
key to store the new passcode and a confirmation message appears. As a safety measure, the relay
requires you to enter a new passcode twice. This ensures the passcode has been entered correctly.
745 SETPOINTS:
Not Programmed
SETPOINT ACCESS:
Read & Write
CHANGE PASSCODE?
No
CHANGE PASSCODE?
Yes
PLEASE ENTER CURRENT
PASSCODE:
PLEASE ENTER A NEW
PASSCODE:
PLEASE ENTER A NEW
PASSCODE:
PLEASE RE-ENTER NEW
PASSCODE:
VALUE
VALUE
ENTER
MESSAGE
VALUE
VALUE
ENTER
ENTER
ENTER
Содержание TRANSFORMER MANAGEMENT RELAY 745