GE Multilin
745 Transformer Management Relay
7-39
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
WINDING 3
NEUTRAL INST
O/C 1
2120
Winding 3 Neutral Inst O/C 1 Function
---
---
---
F30
0 = Disabled
2121
Winding 3 Neutral Inst O/C 1 Target
---
---
---
F46
1 = Latched
2122
Winding 3 Neutral Inst O/C 1 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2123
Winding 3 Neutral Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2124
Winding 3 Neutral Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2125
Reserved
↓
↓
↓
↓
↓
↓
↓
212F
Reserved
WINDING 1
NEUTRAL INST
O/C 2
2130
Winding 1 Neutral Inst O/C 2 Function
---
---
---
F30
0 = Disabled
2131
Winding 1 Neutral Inst O/C 2 Target
---
---
---
F46
1 = Latched
2132
Winding 1 Neutral Inst O/C 2 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2133
Winding 1 Neutral Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
2134
Winding 1 Neutral Inst O/C 2 Block
---
---
---
F87
0 = Disabled
2135
Reserved
↓
↓
↓
↓
↓
↓
↓
213F
Reserved
WINDING 2
NEUTRAL INST
O/C 2
2140
Winding 2 Neutral Inst O/C 2 Function
---
---
---
F30
0 = Disabled
2141
Winding 2 Neutral Inst O/C 2 Target
---
---
---
F46
1 = Latched
2142
Winding 2 Neutral Inst O/C 2 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2143
Winding 2 Neutral Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
2144
Winding 2 Neutral Inst O/C 2 Block
---
---
---
F87
0 = Disabled
2145
Reserved
↓
↓
↓
↓
↓
↓
↓
214F
Reserved
WINDING 3
NEUTRAL INST
O/C 2
2150
Winding 3 Neutral Inst O/C 2 Function
---
---
---
F30
0 = Disabled
2151
Winding 3 Neutral Inst O/C 2 Target
---
---
---
F46
1 = Latched
2152
Winding 3 Neutral Inst O/C 2 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2153
Winding 3 Neutral Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
2154
Winding 3 Neutral Inst O/C 2 Block
---
---
---
F87
0 = Disabled
2155
Reserved
↓
↓
↓
↓
↓
↓
↓
215F
Reserved
WINDING 1
GROUND TIME
O/C
2160
Winding 1 Ground Time O/C Function
---
---
---
F30
1 = Enabled
2161
Winding 1 Ground Time O/C Target
---
---
---
F46
1 = Latched
2162
Winding 1 Ground Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
85 = 0.85
×
CT
2163
Winding 1 Ground Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2164
Winding 1 Ground Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2165
Winding 1 Ground Time O/C Reset
---
---
---
F68
1 = Linear
2166
Winding 1 Ground Time O/C Block
---
---
---
F87
0 = Disabled
2167
Reserved
↓
↓
↓
↓
↓
↓
↓
216F
Reserved
WINDING 2
GROUND TIME
O/C
2170
Winding 2 Ground Time O/C Function
---
---
---
F30
0 = Disabled
2171
Winding 2 Ground Time O/C Target
---
---
---
F46
1 = Latched
2172
Winding 2 Ground Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
85 = 0.85
×
CT
2173
Winding 2 Ground Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2174
Winding 2 Ground Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2175
Winding 2 Ground Time O/C Reset
---
---
---
F68
1 = Linear
2176
Winding 2 Ground Time O/C Block
---
---
---
F87
0 = Disabled
2177
Reserved
↓
↓
↓
↓
↓
↓
↓
217F
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 27 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT