7-38
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
WINDING 3
PHASE INST
O/C 2
20C0
Winding 3 Phase Inst O/C 2 Function
---
---
---
F30
1 = Enabled
20C1
Winding 3 Phase Inst O/C 2 Target
---
---
---
F46
1 = Latched
20C2
Winding 3 Phase Inst O/C 2 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
20C3
Winding 3 Phase Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
20C4
Winding 3 Phase Inst O/C 2 Block
---
---
---
F87
0 = Disabled
20C5
Reserved
↓
↓
↓
↓
↓
↓
↓
20CF
Reserved
WINDING 1
NEUTRAL TIME
O/C
20D0
Winding 1 Neutral Time O/C Function
---
---
---
F30
1 = Enabled
20D1
Winding 1 Neutral Time O/C Target
---
---
---
F46
1 = Latched
20D2
Winding 1 Neutral Time O/C Pickup
0.05 to 20.00
0.01
x CT
F3
85 = 0.85 x CT
20D3
Winding 1 Neutral Time O/C Shape
---
---
---
F36
0 = Ext Inverse
20D4
Winding 1 Neutral Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
20D5
Winding 1 Neutral Time O/C Reset
---
---
---
F68
1 = Linear
20D6
Winding 1 Neutral Time O/C Block
---
---
---
F87
0 = Disabled
20D7
Reserved
↓
↓
↓
↓
↓
↓
↓
20DF
Reserved
WINDING 2
NEUTRAL TIME
O/C
20E0
Winding 2 Neutral Time O/C Function
---
---
---
F30
0 = Disabled
20E1
Winding 2 Neutral Time O/C Target
---
---
---
F46
1 = Latched
20E2
Winding 2 Neutral Time O/C Pickup
0.05 to 20.00
0.01
x CT
F3
85 = 0.85 x CT
20E3
Winding 2 Neutral Time O/C Shape
---
---
---
F36
0 = Ext Inverse
20E4
Winding 2 Neutral Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
20E5
Winding 2 Neutral Time O/C Reset
---
---
---
F68
1 = Linear
20E6
Winding 2 Neutral Time O/C Block
---
---
---
F87
0 = Disabled
20E7
Reserved
↓
↓
↓
↓
↓
↓
↓
20EF
Reserved
WINDING 3
NEUTRAL TIME
O/C
20F0
Winding 3 Neutral Time O/C Function
---
---
---
F30
0 = Disabled
20F1
Winding 3 Neutral Time O/C Target
---
---
---
F46
1 = Latched
20F2
Winding 3 Neutral Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
85 = 0.85
×
CT
20F3
Winding 3 Neutral Time O/C Shape
---
---
---
F36
0 = Ext Inverse
20F4
Winding 3 Neutral Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
20F5
Winding 3 Neutral Time O/C Reset
---
---
---
F68
1 = Linear
20F6
Winding 3 Neutral Time O/C Block
---
---
---
F87
0 = Disabled
20F7
Reserved
↓
↓
↓
↓
↓
↓
↓
20FF
Reserved
WINDING 1
NEUTRAL INST
O/C 1
2100
Winding 1 Neutral Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2101
Winding 1 Neutral Inst O/C 1 Target
---
---
---
F46
1 = Latched
2102
Winding 1 Neutral Inst O/C 1 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2103
Winding 1 Neutral Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2104
Winding 1 Neutral Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2105
Reserved
↓
↓
↓
↓
↓
↓
↓
210F
Reserved
WINDING 2
NEUTRAL INST
O/C 1
2110
Winding 2 Neutral Inst O/C 1 Function
---
---
---
F30
0 = Disabled
2111
Winding 2 Neutral Inst O/C 1 Target
---
---
---
F46
1 = Latched
2112
Winding 2 Neutral Inst O/C 1 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2113
Winding 2 Neutral Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2114
Winding 2 Neutral Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2115
Reserved
↓
↓
↓
↓
↓
↓
↓
211F
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 26 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Содержание TRANSFORMER MANAGEMENT RELAY 745
Страница 2: ...Courtesy of NationalSwitchgear com ...