5-40
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
5.6.2 SETPOINT GROUP
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
Ö
SETPOINT GROUP
Each protection and monitoring element setpoint (programmed in
S4 ELEMENTS
) has four copies, and these settings are
organized in four setpoint groups. Only one group of settings are active in the protection scheme at a time. The active
group can be selected using the
ACTIVE SETPOINT GROUP
setpoint or using a logic input. The setpoints in any group can be
viewed or edited using the
EDIT SETPOINT GROUP
setpoint.
•
ACTIVE SETPOINT GROUP
: Select the number of the
SETPOINT GROUP
whose settings are to be active in the protec-
tion scheme. This selection will be overridden if a higher number setpoint group is activated using logic inputs.
•
EDIT SETPOINT GROUP
: Select the number of the
SETPOINT GROUP
whose settings are to be viewed and/or edited
via the front panel keypad or any of the communication ports. Selecting "Active Group" selects the currently active set-
point group for editing.
•
GROUP 2(4) ACTIVATE SIGNAL
: Select any logic input which, when asserted, will (remotely) select
SETPOINT GROUP
2(4)
to be the active group. This selection will be overridden if a higher number setpoint group is activated using the
ACTIVE SETPOINT GROUP
setpoint or another logic input.
5.6.3 DIFFERENTIAL ELEMENT
a) MAIN MENU
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
DIFFERENTIAL
This section contains the settings to configure the percent differential element, including all associated harmonic inhibit fea-
tures. The 745 provides three independent harmonic inhibit features:
HARMONIC INHIBIT
, which implements an inhibit
scheme based on 2nd or 2nd + 5th harmonic which is ‘in-circuit’ at all times;
ENERGIZATION INHIBIT
, which allows changing
the characteristics of the inhibit scheme during energization to improve reliability; and
5TH HARMONIC INHIBIT
, which imple-
ments an inhibit scheme based on 5th harmonic only, allowing inhibiting the percent differential during intentional overexci-
tation of the system.
SETPOINT GROUP
[ENTER] for more
ACTIVE SETPOINT
GROUP: Group 1
Range: Group 1, Group 2, Group 3, Group 4
EDIT SETPOINT
GROUP: Active Group
Range: Group 1, Group 2, Group 3, Group 4,
Active Group
GROUP 2 ACTIVATE
SIGNAL: Disabled
Range: Logic Input 1 to 16, Disabled
GROUP 3 ACTIVATE
SIGNAL: Disabled
Range: Logic Input 1 to 16, Disabled
GROUP 4 ACTIVATE
SIGNAL: Disabled
Range: Logic Input 1 to 16, Disabled
DIFFERENTIAL
[ENTER] for more
PERCENT DIFFERENTL
[ENTER] for more
See page 5–41.
HARMONIC INHIBIT
[ENTER] for more
See page 5–43.
ENERGIZATN INHIBIT
[ENTER] for more
See page 5–44.
5th HARM INHIBIT
[ENTER] for more
See page 5–47.
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE