7-36
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
HARMONIC
INHIBIT
2008
Harmonic Inhibit Function
---
---
---
F30
1 = Enabled
2009
Harmonic Inhibit Parameters
---
---
---
F64
0 = 2nd
200A
Harmonic Averaging
---
---
---
F30
0 = Disabled
200B
Harmonic Inhibit Level
0.1 to 65.0
0.1
% ƒo
F2
200 = 20.0% ƒo
200C
Reserved
ENERGI-
ZATION
INHIBIT
200D
Energization Inhibit Function
---
---
---
F30
1 = Enabled
200E
Energization Inhibit Parameters
---
---
---
F64
0 = 2nd
200F
Harmonic Averaging
---
---
---
F30
1 = Enabled
2010
Energization Inhibit Level
0.1 to 65.0
0.1
% ƒo
F2
200 = 20.0% ƒo
2011
Energization Inhibit Duration
0.05 to 600.00
0.01
s
F1
10 = 0.10 s
2012
Energization Sensing By Current
---
---
---
F30
1 = Enabled
2013
Minimum Energization Current
0.10 to 0.50
0.01
×
CT
F3
10 = 0.10
×
CT
2014
Energization Sensing By Voltage
---
---
---
F30
0 = Disabled
2015
Minimum Energization Voltage
0.50 to 0.99
0.01
×
VT
F3
85 = 0.85
×
VT
2016
Breakers Are Open Signal
---
---
---
F88
0 = Disabled
2017
Parallel Transformer Breaker Close Signal
---
---
---
F88
0 = Disabled
2018
Reserved
5TH
HARMONIC
INHIBIT
2019
5th Harmonic Inhibit Function
---
---
---
F30
0 = Disabled
201A
Harmonic Averaging
---
---
---
F30
0 = Disabled
201B
5th Harmonic Inhibit Level
0.1 to 65.0
0.1
% ƒo
F2
100 = 10.0% ƒo
201C
Reserved
↓
↓
↓
↓
↓
↓
↓
201F
Reserved
INST
DIFFERENTIAL
2020
Inst Differential Function
---
---
---
F30
1 = Enabled
2021
Inst Differential Target
---
---
---
F46
1 = Latched
2022
Inst Differential Pickup
3.00 to 20.00
0.01
×
CT
F3
800 = 8.00
×
CT
2023
Inst Differential Block
---
---
---
F87
0 = Disabled
2024
Reserved
↓
↓
↓
↓
↓
↓
↓
203F
Reserved
WINDING 1
PHASE TIME
O/C
2040
Winding 1 Phase Time O/C Function
---
---
---
F30
1 = Enabled
2041
Winding 1 Phase Time O/C Target
---
---
---
F46
1 = Latched
2042
Winding 1 Phase Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
120 = 1.20
×
CT
2043
Winding 1 Phase Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2044
Winding 1 Phase Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2045
Winding 1 Phase Time O/C Reset
---
---
---
F68
1 = Linear
2046
Winding 1 Phase Time O/C Block
---
---
---
F87
0 = Disabled
2047
Winding 1 Harmonic Derating Correction
---
---
---
F30
0 = Disabled
2048
Reserved
↓
↓
↓
↓
↓
↓
↓
204F
Reserved
WINDING 2
PHASE TIME
O/C
2050
Winding 2 Phase Time O/C Function
---
---
---
F30
1 = Enabled
2051
Winding 2 Phase Time O/C Target
---
---
---
F46
1 = Latched
2052
Winding 2 Phase Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
120 = 1.20
×
CT
2053
Winding 2 Phase Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2054
Winding 2 Phase Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2055
Winding 2 Phase Time O/C Reset
---
---
---
F68
1 = Linear
2056
Winding 2 Phase Time O/C Block
---
---
---
F87
0 = Disabled
2057
Winding 2 Harmonic Derating Correction
---
---
---
F30
0 = Disabled
2058
Reserved
↓
↓
↓
↓
↓
↓
↓
205F
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 24 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT