5-48
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
5.6.4 INSTANTANEOUS DIFFERENTIAL
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
INST DIFFERENTIAL
This section contains the settings to configure the (unrestrained) instantaneous differential element, for protection under
high magnitude internal faults.
•
INST DIFFERENTIAL PICKUP
: Enter the level of differential current (in units of relay nominal current) above which the
instantaneous differential element will pickup and operate.
Figure 5–13: INSTANTANEOUS DIFFERENTIAL SCHEME LOGIC
INST DIFFERENTIAL
[ENTER] for more
INST DIFFERENTIAL
FUNCTION: Enabled
Range: Enabled, Disabled
INST DIFFERENTIAL
TARGET: Latched
Range: Self-Reset, Latched, None
INST DIFFERENTIAL
PICKUP: 8.00 x CT
Range: 3.00 to 20.00 in steps of 0.01
INST DIFFERENTIAL
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE