745 Transformer Management Relay
7-41
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
WINDING 1
RESTD GND
FAULT
21E5
Reserved
↓
↓
↓
↓
↓
↓
↓
21EF
Reserved
21F0
Winding 1 Restricted Ground Fault Function
---
---
---
F30
0 = Disabled
21F1
Winding 1 Restricted Ground Fault Target
---
---
---
F46
1 = Latched
21F2
Winding 1 Restricted Ground Fault Pickup
0.02 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
21F3
Winding 1 Restricted Ground Fault Slope
0 to 100
1
%
F1
10%
21F4
Winding 1 Restricted Ground Fault Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
21F5
Winding 1 Restricted Ground Fault Block
---
---
---
F87
0 = Disabled
21F6
Reserved
↓
↓
↓
↓
↓
↓
↓
21FF
Reserved
WINDING 2
RESTD GND
FAULT
2200
Winding 2 Restricted Ground Fault Function
---
---
---
F30
0 = Disabled
2201
Winding 2 Restricted Ground Fault Target
---
---
---
F46
1 = Latched
2202
Winding 2 Restricted Ground Fault Pickup
0.02 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
2203
Winding 2 Restricted Ground Fault Slope
0 to 100
1
%
F1
10%
2204
Winding 2 Restricted Ground Fault Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
2205
Winding 2 Restricted Ground Fault Block
---
---
---
F87
0 = Disabled
2206
Reserved
↓
↓
↓
↓
↓
↓
↓
220F
Reserved
WINDING 3
RESTD GND
FAULT
2210
Winding 3 Restricted Ground Fault Function
---
---
---
F30
0 = Disabled
2211
Winding 3 Restricted Ground Fault Target
---
---
---
F46
1 = Latched
2212
Winding 3 Restricted Ground Fault Pickup
0.02 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
2213
Winding 3 Restricted Ground Fault Slope
0 to 100
1
%
F1
10%
2214
Winding 3 Restricted Ground Fault Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
2215
Winding 3 Restricted Ground Fault Block
---
---
---
F87
0 = Disabled
2216
Reserved
↓
↓
↓
↓
↓
↓
↓
2245
Reserved
WINDING 1
NEG SEQ TIME
O/C
2246
Reserved
↓
↓
↓
↓
↓
↓
↓
224F
Reserved
2250
Winding 1 Neg Seq Time O/C Function
---
---
---
F30
0 = Disabled
2251
Winding 1 Neg Seq Time O/C Target
---
---
---
F46
1 = Latched
2252
Winding 1 Neg Seq Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
25 = 0.25
×
CT
2253
Winding 1 Neg Seq Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2254
Winding 1 Neg Seq Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2255
Winding 1 Neg Seq Time O/C Reset
---
---
---
F68
1 = Linear
2256
Winding 1 Neg Seq Time O/C Block
---
---
---
F87
0 = Disabled
2257
Reserved
↓
↓
↓
↓
↓
↓
↓
225F
Reserved
WINDING 2
NEG SEQ TIME
O/C
2260
Winding 2 Neg Seq Time O/C Function
---
---
---
F30
0 = Disabled
2261
Winding 2 Neg Seq Time O/C Target
---
---
---
F46
1 = Latched
2262
Winding 2 Neg Seq Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
25 = 0.25
×
CT
2263
Winding 2 Neg Seq Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2264
Winding 2 Neg Seq Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2265
Winding 2 Neg Seq Time O/C Reset
---
---
---
F68
1 = Linear
2266
Winding 2 Neg Seq Time O/C Block
---
---
---
F87
0 = Disabled
2267
Reserved
↓
↓
↓
↓
↓
↓
↓
226F
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 29 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT