GE Multilin
745 Transformer Management Relay
7-37
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
WINDING 3
PHASE TIME
O/C
2060
Winding 3 Phase Time O/C Function
---
---
---
F30
1 = Enabled
2061
Winding 3 Phase Time O/C Target
---
---
---
F46
1 = Latched
2062
Winding 3 Phase Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
120 = 1.20
×
CT
2063
Winding 3 Phase Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2064
Winding 3 Phase Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2065
Winding 3 Phase Time O/C Reset
---
---
---
F68
1 = Linear
2066
Winding 3 Phase Time O/C Block
---
---
---
F87
0 = Disabled
2067
Winding 3 Harmonic Derating Correction
---
---
---
F30
0 = Disabled
2068
Reserved
↓
↓
↓
↓
↓
↓
↓
206F
Reserved
WINDING 1
PHASE INST
O/C 1
2070
Winding 1 Phase Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2071
Winding 1 Phase Inst O/C 1 Target
---
---
---
F46
1 = Latched
2072
Winding 1 Phase Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
1000 = 10.00 x
CT
2073
Winding 1 Phase Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2074
Winding 1 Phase Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2075
Reserved
↓
↓
↓
↓
↓
↓
↓
207F
Reserved
WINDING 2
PHASE INST
O/C 1
2080
Winding 2 Phase Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2081
Winding 2 Phase Inst O/C 1 Target
---
---
---
F46
1 = Latched
2082
Winding 2 Phase Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
10.00 x CT
2083
Winding 2 Phase Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2084
Winding 2 Phase Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2085
Reserved
↓
↓
↓
↓
↓
↓
↓
208F
Reserved
WINDING 3
PHASE INST
O/C 1
2090
Winding 3 Phase Inst O/C 1 Function
---
---
---
F30
1 = Enabled
2091
Winding 3 Phase Inst O/C 1 Target
---
---
---
F46
1 = Latched
2092
Winding 3 Phase Inst O/C 1 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
2093
Winding 3 Phase Inst O/C 1 Delay
0 to 60000
1
ms
F1
0 ms
2094
Winding 3 Phase Inst O/C 1 Block
---
---
---
F87
0 = Disabled
2095
Reserved
↓
↓
↓
↓
↓
↓
↓
209F
Reserved
WINDING 1
PHASE INST
O/C 2
20A0
Winding 1 Phase Inst O/C 2 Function
---
---
---
F30
1 = Enabled
20A1
Winding 1 Phase Inst O/C 2 Target
---
---
---
F46
1 = Latched
20A2
Winding 1 Phase Inst O/C 2 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
20A3
Winding 1 Phase Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
20A4
Winding 1 Phase Inst O/C 2 Block
---
---
---
F87
0 = Disabled
20A5
Reserved
↓
↓
↓
↓
↓
↓
↓
20AF
Reserved
WINDING 2
PHASE INST
O/C 2
20B0
Winding 2 Phase Inst O/C 2 Function
---
---
---
F30
1 = Enabled
20B1
Winding 2 Phase Inst O/C 2 Target
---
---
---
F46
1 = Latched
20B2
Winding 2 Phase Inst O/C 2 Pickup
0.05 to 20.00
0.01
x CT
F3
1000=10.00 x CT
20B3
Winding 2 Phase Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
20B4
Winding 2 Phase Inst O/C 2 Block
---
---
---
F87
0 = Disabled
20B5
Reserved
↓
↓
↓
↓
↓
↓
↓
20BF
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 25 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT