5 SETPOINTS
5.6 S4 ELEMENTS
5
e) 5TH HARMONIC INHIBIT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
DIFFERENTIAL
ÖØ
5th HARM INHIBIT
The 5
th
harmonic inhibit feature of the percent differential element allows inhibiting the percent differential during intentional
overexcitation of the system. This feature inhibits the percent differential element in a particular phase if the 5
th
harmonic of
the same phase exceeds the harmonic inhibit level setting. With harmonic averaging enabled, all three phases are inhibited
if the three-phase average of the 5
th
harmonic exceeds the level setting.
•
HARMONIC AVERAGING
: Select "Enabled" to use the three-phase average of the 5th harmonic current against the
harmonic inhibit setting.
•
5th HARMONIC INHIBIT LEVEL
: Enter the level of 5th harmonic current above which the percent differential element
will be inhibited from operating.
Figure 5–12: 5TH HARMONIC INHIBIT SCHEME LOGIC
5th HARM INHIBIT
[ENTER] for more
5th HARMONIC INHIBIT
FUNCTION: Enabled
Range: Enabled, Disabled
HARMONIC AVERAGING:
Disabled
Range: 0.10 to 0.50 x CT in steps of 0.01
5th HARMONIC INHIBIT
LEVEL: 10.0% f0
Range: 0.1 to 65.0% f
0
in steps of 0.1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE