GE Multilin
745 Transformer Management Relay
5-75
5 SETPOINTS
5.6 S4 ELEMENTS
5
c) VOLTS-PER-HERTZ
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
OVEREXCITATION
ÖØ
VOLTS-PER-HERTZ 1(2)
The V/Hz element uses the ratio of the actual measured voltage at the voltage terminal and the measured system fre-
quency. For example, a measured phases-to-phase voltage of 120 volts at 60 Hz, results in a ratio of 2 V/Hz. For 115%
overload, the setting of the V/Hz minimum pickup would be 2.3 V/Hz.
The element has a linear reset characteristic. The reset time can be programmed to match the cooling characteristic of the
protected equipment. The element will fully reset after the
VOLTS-PER-HERTZ RESET
value. The V/Hz function can be used
as an instantaneous element with no intentional delay, as a definite time element, or as an inverse timed element.
•
MINIMUM OPERATING VOLTAGE
: Enter the minimum value of voltage (in terms of nominal VT secondary voltage)
required to allow the Volts-per-Hertz 1 element to operate.
•
VOLTS-PER-HERTZ 1 PICKUP
: Enter the volts-per-hertz value (in V/Hz) above which the Volts-per-Hertz 1 element
will pickup and start the delay timer.
•
VOLTS-PER-HERTZ 1 SHAPE
: Select the curve shape to be used for the Volts-per-Hertz 1 element. The inverse
volts-per-hertz curve shapes are shown below.
•
VOLTS-PER-HERTZ 1 DELAY
: Enter the time that the volts-per-hertz value must remain above the pickup level before
the element operates.
•
VOLTS-PER-HERTZ 1 RESET
: Enter the time that the volts-per-hertz value must remain below the pickup level before
the element resets.
VOLTS-PER-HERTZ 1
[ENTER] for more
VOLTS-PER-HERTZ 1
FUNCTION: Disabled
Range: Enabled, Disabled
VOLTS-PER-HERTZ 1
TARGET: Self-Reset
Range: Self-Reset, Latched, None
MINIMUM OPERATING
VOLTAGE: 0.10 x VT
Range: 0.10 to 0.99 x VT in steps of 0.01
VOLTS-PER-HERTZ 1
PICKUP: 2.36 V/Hz
Range: 1.00 to 4.00 V/Hz in steps of 0.01
VOLTS-PER-HERTZ 1
SHAPE: Definite Time
Range: Definite Time, Inv Curve 1, Inv Curve 2,
Inv Curve 3
VOLTS-PER-HERTZ 1
DELAY: 2.00 s
Range: 0.00 to 600.00 s in steps of 0.01
VOLTS-PER-HERTZ 1
RESET:
0.0 s
Range: 0.0 to 6000.0 s in steps of 0.1
VOLTS-PER-HERTZ 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE