5-78
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
b) THD LEVEL
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
HARMONICS
Ö
W1(3) THD LEVEL
•
MINIMUM OPERATING CURRENT
: Enter the minimum value of current (in units of relay nominal current) required to
allow the THD level element to operate.
•
W1(3) THD PICKUP LEVEL
: Enter the total harmonic distortion (in %ƒ
0
) above which the Winding 1(3) Total Harmonic
Distortion element level will pickup and start the delay timer.
•
W1(3) THD LEVEL DELAY
: Enter the time that the total harmonic distortion must remain above the pickup level before
the element operates.
Figure 5–34: THD LEVEL SCHEME LOGIC
W1 THD LEVEL
[ENTER] for more
W1 THD LEVEL
FUNCTION: Disabled
Range: Enabled, Disabled
W1 THD LEVEL
TARGET: Self-Reset
Range: Self-Reset, Latched, None
MINIMUM OPERATING
CURRENT: 0.10 x CT
Range: 0.03 to 1.00 x CT in steps of 0.01
W1 THD LEVEL
PICKUP: 50.0% f0
Range: 0.1 to 50.0% f
0
in steps of 0.1
W1 THD LEVEL
DELAY: 10 s
Range: 0 to 60000 s in steps of 1
W1 THD LEVEL
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE