7-52
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
F33
16 bits
ASCII TEXT CHARACTERS
xxxx xxxx 1111 1111
Second ASCII Character
1111 1111 xxxx xxxx
First ASCII Character
F34
16 bits
RELAY STATE
0000 0000 0000 0000
0 = De-energized
0000 0000 0000 0001
1 = Energized
F35
16 bits
CONDITIONS
xxxx xxxx xxxx xxx1
Trip (0 = No Active Trip Condition,
1 = Active Trip Condition)
xxxx xxxx xxxx xx1x
Alarm
(0=No Active Alarm Conditions,
1=Active Alarm Condition(s))
xxxx xxxx xxxx x1xx
Pickup
(0 = No Pickup, 1 = Pickup)
xxxx xxxx xxx1 xxxx
Phase A (1 = Phase A Fault)
xxxx xxxx xx1x xxxx
Phase B (1 = Phase B Fault)
xxxx xxxx x1xx xxxx
Phase C (1 = Phase C Fault)
xxxx xxxx 1xxx xxxx
Ground (1 = Ground Fault)
F36
16 bits
OVERCURRENT CURVE SHAPE
0000 0000 0000 0000
0 = Ext Inverse
0000 0000 0000 0001
1 = Very Inverse
0000 0000 0000 0010
2 = Norm Inverse
0000 0000 0000 0011
3 = Mod Inverse
0000 0000 0000 0100
4 = Definite Time
0000 0000 0000 0101
5 = IEC Curve A
0000 0000 0000 0110
6 = IEC Curve B
0000 0000 0000 0111
7 = IEC Curve C
0000 0000 0000 1000
8 = IEC Short In
0000 0000 0000 1001
9 = IAC Ext Inv
0000 0000 0000 1010
10 = IAC Very Inv
0000 0000 0000 1011
11 = IAC Inverse
0000 0000 0000 1100
12 = IAC Short Inv
0000 0000 0000 1101
13 = FlexCurve A
0000 0000 0000 1110
14 = FlexCurve B
0000 0000 0000 1111
15 = FlexCurve C
F37
16 bits
RATED WINDING TEMP RISE
0000 0000 0000 0000
0 = 55° C (oil)
0000 0000 0000 0001
1 = 65° C (oil)
0000 0000 0000 0010
2 = 80° C (dry)
0000 0000 0000 0011
3 = 115° C (dry)
0000 0000 0000 0100
4 = 150° C (dry)
F38
16 bits
OUTPUT TYPE
0000 0000 0000 0000
0 = Trip
0000 0000 0000 0001
1 = Alarm
0000 0000 0000 0010
2 = Control
F39
16 bits
COOLING TYPE FOR OIL-FILLED
TRANSFORMER
0000 0000 0000 0000
0 = OA
0000 0000 0000 0001
1 = FA
0000 0000 0000 0010
2 = Non-Directed FOA/FOW
0000 0000 0000 0011
3 = Directed FOA/FOW
F40
16 bits
WINDING SELECTION
0000 0000 0000 0000
0 = None
0000 0000 0000 0001
1 = Winding 1
0000 0000 0000 0010
2 = Winding 2
0000 0000 0000 0011
3 = Winding 3
Table 7–6: 745 DATA FORMATS (Sheet 9 of 25)
CODE
APPLICABLE BITS
DEFINITION
F41
16 bits
RTD TYPE
0000 0000 0000 0000
0 = 100 ohm Platinum
0000 0000 0000 0001
1 = 120 ohm Nickel
0000 0000 0000 0010
2 = 100 ohm Nickel
0000 0000 0000 0011
3 = Monthly Average
F42
16 bits
ANALOG INPUT RANGE
0000 0000 0000 0000
0 = 0-1 mA
0000 0000 0000 0001
1 = 0-5 mA
0000 0000 0000 0010
2 = 4-20 mA
0000 0000 0000 0011
3 = 0-20 mA
F43
16 bits
NOT ASSERTED / ASSERTED
0000 0000 0000 0000
0 = Not Asserted
0000 0000 0000 0001
1 = Asserted
F44
16 bits
OPERATION STATUS
xxxx xxxx xxxx xxx1
Code Programming Mode
(0 = Disabled, 1 = Enabled)
xxxx xxxx xxxx xx1x
Setpoint Access Jumper
(0 = Disabled, 1 = Enabled)
xxxx xxxx xxxx x1xx
Factory Service Mode
(0 = Disabled, 1 = Enabled)
xxxx xxxx xxxx 1xxx
Comm Port Passcode Access
(0 = Read & Write, 1 = Read Only)
F45
16 bits
ANALOG OUTPUT VALUE
0000 0000 0000 0000
0 = W1 øA Current
0000 0000 0000 0001
1 = W1 øB Current
0000 0000 0000 0010
2 = W1 øC Current
0000 0000 0000 0011
3 = W2 øA Current
0000 0000 0000 0100
4 = W2 øB Current
0000 0000 0000 0101
5 = W2 øC Current
0000 0000 0000 0110
6 = W3 øA Current
0000 0000 0000 0111
7 = W3 øB Current
0000 0000 0000 1000
8 = W3 øC Current
0000 0000 0000 1001
9 = W1 Loading
0000 0000 0000 1010
10 = W2 Loading
0000 0000 0000 1011
11 = W3 Loading
0000 0000 0000 1100
12 = W1 øA THD
0000 0000 0000 1101
13 = W1 øB THD
0000 0000 0000 1110
14 = W1 øC THD
0000 0000 0000 1111
15 = W2 øA THD
0000 0000 0001 0000
16 = W2 øB THD
0000 0000 0001 0001
17 = W2 øC THD
0000 0000 0001 0010
18 = W3 øA THD
0000 0000 0001 0011
19 = W3 øB THD
0000 0000 0001 0100
20 = W3 øC THD
0000 0000 0001 0101
21 = W1 Derating
0000 0000 0001 0110
22 = W2 Derating
0000 0000 0001 0111
23 = W3 Derating
0000 0000 0001 1000
24 = Frequency
0000 0000 0001 1001
25 = Tap Position
0000 0000 0001 1010
26 = Voltage
0000 0000 0001 1011
27 = W1 øA Demand
0000 0000 0001 1100
28 = W1 øB Demand
0000 0000 0001 1101
29 = W1 øC Demand
0000 0000 0001 1110
30 = W2 øA Demand
0000 0000 0001 1111
31 = W2 øB Demand
0000 0000 0010 0000
32 = W2 øC Demand
0000 0000 0010 0001
33 = W3 øA Demand
0000 0000 0010 0010
34 = W3 øB Demand
Table 7–6: 745 DATA FORMATS (Sheet 10 of 25)
CODE
APPLICABLE BITS
DEFINITION