GE Multilin
745 Transformer Management Relay
5-55
5 SETPOINTS
5.6 S4 ELEMENTS
5
d) WINDING 1(3) PHASE INSTANTANEOUS OVERCURRENT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
PHASE OC
ÖØ
W1(3) PHASE INST OC 1(2)
•
W1(3) PHASE INST OC 1(2) PICKUP
: Enter the level of phase current (in units of relay nominal current) above which
the Winding 1(3) Phase Instantaneous Overcurrent 1 element will pickup and start the delay timer.
•
W1(3) PHASE INST OC 1(2) DELAY
: Enter the time that the phase current must remain above the pickup level before
the element operates.
The setpoint messages
above and the following logic diagram are identical for the PHASE INSTANTA-
NEOUS OVERCURRENT 2 element.
Figure 5–16: PHASE IOC 1 SCHEME LOGIC
W1 PHASE INST OC 1
[ENTER] for more
W1 PHASE INST OC 1
FUNCTION: Enabled
Range: Enabled, Disabled
W1 PHASE INST OC 1
TARGET: Latched
Range: Self-Reset, Latched, None
W1 PHASE INST OC 1
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 x CT in steps of 0.01
W1 PHASE INST OC 1
DELAY: 0 ms
Range: 0 to 60000 ms in steps of 1
W1 PHASE INST OC 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
NOTE