5 SETPOINTS
5.6 S4 ELEMENTS
5
Figure 5–30: FREQUENCY DECAY SCHEME LOGIC
d) OVERFREQUENCY
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
FREQUENCY
ÖØ
OVERFREQUENCY
OVERFREQUENCY
[ENTER] for more
OVERFREQUENCY
FUNCTION: Disabled
Range: Enabled, Disabled
OVERFREQUENCY
TARGET: Latched
Range: Self-Reset, Latched, None
CURRENT SENSING:
Enabled
Range: Enabled, Disabled
MINIMUM OPERATING
CURRENT: 0.20 x CT
Range: 0.20 to 1.00 x CT in steps of 0.01
MINIMUM OPERATING
VOLTAGE: 0.50 x VT
Range: 0.10 to 0.99 x CT in steps of 0.01
OVERFREQUENCY
PICKUP: 60.50 Hz
Range: 50.01 to 65.00 Hz in steps of 0.01
OVERFREQUENCY
DELAY: 5.00 s
Range: 0.00 to 600.00 s in steps of 0.01
OVERFREQUENCY
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE