8-10
745 Transformer Management Relay
GE Multilin
8.4 DISPLAY, METERING, COMMUNICATIONS, AND ANALOG OUTPUTS
8 COMMISSIONING
8
b) DETAILED CALIBRATION OF RTD INPUT
1.
Alter the following setpoints. Set
S2 SYSTEM SETUP
ÖØ
AMBIENT TEMP
Ö
AMBIENT TEMPERATURE SENSING
to "Enabled"
and set
S2 SYSTEM SETUP
ÖØ
AMBIENT TEMP
ÖØ
AMBIENT RTD TYPE
to the desired type.
2.
The measured values should be ±2°C or ±4°F. Alter the resistance applied to the RTD input (note the 3-input connec-
tion must be used for the measurements to be valid) as per the
typical
table below to simulate RTDs and verify accu-
racy of the measured values. View the measured values in
A2 METERING
ÖØ
AMBIENT TEMP
Ö
AMBIENT TEMPERATURE
.
Refer to RTD tables included in this manual for calibration of resistance versus temperature.
c) AMBIENT TEMPERATURE BY MONTHLY AVERAGES
1.
If the ambient temperature is entered as 12 monthly averages, program the value for the month during which the relay
is being commissioned.
2.
Examine the
A2 METERING
ÖØ
AMBIENT TEMP
Ö
AMBIENT TEMPERATURE
actual value to verify the programmed temper-
ature.
3.
Verify that values entered for other months do not affect the value for the present month.
Table 8–1: MEASURED RTD TEMPERATURE
RTD TYPE
100
Ω
PLATINUM
RESISTANCE
EXPECTED RTD READING
MEASURED RTD TEMPERATURE
____°C ____°F (SELECT ONE)
°C
°F
100
Ω
Platinum
80.31
–50
–58
100.00
0 32
119.39
50 122
138.50
100 212
157.32
150 302
175.84
200 392
194.08
250 482
120
Ω
Nickel
86.17
–50
–58
120.0
0 32
157.74
50 122
200.64
100 212
248.95
150 302
303.46
200 392
366.53
250 482
100
Ω
Nickel
71.81
–50
–58
100.00
0 32
131.45
50 122
167.20
100 212
207.45
150 302
252.88
200 392
305.44
250 482