5-44
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
•
HARMONIC AVERAGING
: Select "Enabled" to use the three-phase average of the harmonic current against the har-
monic inhibit setting. For most applications, enabling harmonic averaging is not recommended.
•
HARMONIC INHIBIT LEVEL
: Enter the level of harmonic current (2
nd
or 2
nd
+5
th
) above which the percent differential
element will be inhibited from operating. For most applications, this level should be set to "20%".
Figure 5–9: HARMONIC INHIBIT SCHEME LOGIC
d) ENERGIZATION INHIBIT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
DIFFERENTIAL
ÖØ
ENERGIZATN INHIBIT
ENERGIZATN INHIBIT
[ENTER] for more
ENERGIZATION INHIBIT
FUNCTION: Enabled
Range: Enabled, Disabled
ENERGIZATION INHIBIT
PARAMETERS: 2nd
Range: 2nd, 2nd + 5th
HARMONIC AVERAGING:
Enabled
Range: Enabled, Disabled
ENERGIZATION INHIBIT
LEVEL: 20.0% f0
Range: 0.1 to 65.0% f
0
in steps of 0.1
ENERGIZATION INHIBIT
DURATION: 0.10 s
Range: 0.05 to 600.00 s in steps of 0.01
MINIMUM ENERGIZATION
CURRENT: 0.10 x CT
Range: 0.10 to 0.50 x CT in steps of 0.01
ENERGIZATION SENSING
BY VOLTAGE: Disabled
Range: Enabled, Disabled
Seen only if Voltage Sensing is enabled.
MINIMUM ENERGIZATION
VOLTAGE: 0.85 x VT
Range: 0.50 to 0.99 x VT in steps of 0.01
Seen only if Voltage Sensing is enabled.
BREAKERS ARE OPEN
SIGNAL: Disabled
Range: Logic Input 1 to 16, Disabled
PARALL XFMR BRKR CLS
SIGNAL: Disabled
Range: Logic Input 1 to 16, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Содержание TRANSFORMER MANAGEMENT RELAY 745
Страница 2: ...Courtesy of NationalSwitchgear com ...