GE Multilin
745 Transformer Management Relay
7-61
7 COMMUNICATIONS
7.5 DNP COMMUNICATIONS
7
7.5DNP COMMUNICATIONS
7.5.1 DEVICE PROFILE DOCUMENT
DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name
: General Electric Multilin Inc.
Device Name
: 745 Transformer Management Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is
described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Analog Input (Object 30, Variations 1, 2, 3 and 4)
Analog Input Change (Object 32, Variations 1, 2, 3 and 4)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
None
Fixed
Configurable (Note 1)
Maximum Application Layer Re-tries:
None
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable (Note 1)
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data
When sending multi-fragment responses
Sometimes
Configurable
Timeouts while waiting for:
Data Link Confirm
None
Fixed
Variable
Configurable (Note 1)
Complete Appl. Fragment
None
Fixed
Variable
Configurable
Application Confirm
None
Fixed
Variable
Configurable
Complete Appl. Response
None
Fixed
Variable
Configurable
Others:
(None)
Executes Control Operations:
WRITE Binary Outputs
Never
Always
Sometimes
Configurable
SELECT/OPERATE
Never
Always
Sometimes
Configurable
DIRECT OPERATE
Never
Always
Sometimes
Configurable
DIRECT OPERATE - NO ACK
Never
Always
Sometimes
Configurable
Count > 1
Never
Always
Sometimes
Configurable
Pulse On
Never
Always
Sometimes
Configurable
Pulse Off
Never
Always
Sometimes
Configurable
Latch On
Never
Always
Sometimes
Configurable
Latch Off
Never
Always
Sometimes
Configurable
(For an explanation of the above, refer to the discussion accompanying Binary Output/Control Relay Output point list)
Queue
Never
Always
Sometimes
Configurable
Clear Queue
Never
Always
Sometimes
Configurable