5-23
5 SETPOINTS
5.3 S1 745 SETUP
5
5.3S1 745 SETUP
5.3.1 PASSCODE
PATH: SETPOINTS
Ö
S1 745 SETUP
Ö
PASSCODE
After installing the setpoint access jumper, a passcode must be entered (if the passcode security feature is enabled) before
setpoints can be changed. When the 745 is shipped from the factory, the passcode is defaulted to 0. When the passcode is
0, the passcode security feature is disabled and only the setpoint access jumper is required for changing setpoints from the
front panel. Passcode entry is also required when programming setpoints from any of the serial communication ports.
•
SETPOINT ACCESS
: This setpoint cannot be edited directly. It indicates whether passcode protection is enabled
("Read Only") or disabled ("Read & Write").
•
RESTRICT SETPOINT WRITE ACCESS
: This setpoint is only displayed when setpoint write access is allowed and
the current passcode is not "0". Select Yes and follow directions to restrict write access. This message is replaced by
ALLOW SETPOINT WRITE ACCESS
when write access is restricted.
•
ALLOW SETPOINT WRITE ACCESS
: This setpoint is only displayed when setpoint write access is restricted. New
setpoints cannot be entered in this state. To gain write access, select Yes and follow directions to enter the previously
programmed passcode. If the passcode is correctly entered, new setpoint entry is allowed. If there is no keypress
within 30 minutes, setpoint write access is automatically restricted. As an additional safety measure, the
SELF-TEST
ERROR: Access Denied
message is generated when the passcode is entered incorrectly three times in a row:
•
CHANGE PASSCODE
: Select "Yes" and follow directions to change the current passcode. Changing the passcode to
the factory default of "0" disables the passcode security feature.
•
ENCRYPTED PASSCODE
: If the programmed passcode is unknown, consult the factory service department with the
encrypted passcode. The passcode can be determined using a deciphering program.
5.3.2 PREFERENCES
PATH: SETPOINTS
Ö
S1 745 SETUP
ÖØ
PREFERENCES
Some relay characteristics can be modified to accommodate the user preferences. This section allows for the definition of
such characteristics.
•
FLASH MESSAGE TIME
: Flash messages are status, warning, error, or information messages displayed for several
seconds, in response to certain key presses during setpoint programming. The time these messages remain on the
display, overriding the normal messages, can be changed to accommodate different user reading rates.
•
DEFAULT MESSAGE TIMEOUT
: After this period of time of no activity on the keys, the 745 automatically begins to
display the programmed set of default messages programmed in
S1 745 SETUP
ÖØ
DEFAULT MESSAGES
.
PASSCODE
[ENTER] for more
SETPOINT ACCESS:
Read & Write
Range: Read Only, Read & Write
This setpoint cannot be edited!
RESTRICT SETPOINT
WRITE ACCESS? No
Range: No, Yes
ALLOW SETPOINT
WRITE ACCESS? No
Range: No, Yes
CHANGE PASSCODE?
No
Range: No, Yes
ENCRYPTED PASSCODE:
AIKFBAIK
Range: Factory Default Passcode is "0"
PREFERENCES
[ENTER] for more
FLASH MESSAGE TIME:
4.0 s
Range: 0.5 to 10.0 s in steps of 0.1
DEFAULT MESSAGE
TIMEOUT: 300 s
Range: 10 to 900 s in steps of 1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE