7-34
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
TIMERS
continued
1D84
Timer 2 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D85
Timer 2 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D86
Timer 3 Start
---
---
---
F62
0 = End
1D87
Timer 3 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D88
Timer 3 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D89
Timer 4 Start
---
---
---
F62
0 = End
1D8A
Timer 4 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D8B
Timer 4 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D8C
Timer 5 Start
---
---
---
F62
0 = End
1D8D
Timer 5 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D8E
Timer 5 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D8F
Timer 6 Start
---
---
---
F62
0 = End
1D90
Timer 6 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D91
Timer 6 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D92
Timer 7 Start
---
---
---
F62
0 = End
1D93
Timer 7 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D94
Timer 7 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D95
Timer 8 Start
---
---
---
F62
0 = End
1D96
Timer 8 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D97
Timer 8 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D98
Timer 9 Start
---
---
---
F62
0 = End
1D99
Timer 9 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D9A
Timer 9 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D9B
Timer 10 Start
---
---
---
F62
0 = End
1D9C
Timer 10 Pickup Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D9D
Timer 10 Dropout Delay
0.00 to 600.00
0.01
s
F3
0.00 s
1D9E
Reserved
↓
↓
↓
↓
↓
↓
↓
1DFF
Reserved
FORCE
OUTPUT
RELAYS
1E00
Force Output Relays Function
---
---
---
F30
0 = Disabled
1E01
Force Output Relay 1
---
---
---
F34
0 = De-energized
1E02
Force Output Relay 2
---
---
---
F34
0 = De-energized
1E03
Force Output Relay 3
---
---
---
F34
0 = De-energized
1E04
Force Output Relay 4
---
---
---
F34
0 = De-energized
1E05
Force Output Relay 5
---
---
---
F34
0 = De-energized
1E06
Force Output Relay 6
---
---
---
F34
0 = De-energized
1E07
Force Output Relay 7
---
---
---
F34
0 = De-energized
1E08
Force Output Relay 8
---
---
---
F34
0 = De-energized
1E09
Force Self-Test Relay
---
---
---
F34
0 = De-energized
1E0A
Reserved
↓
↓
↓
↓
↓
↓
↓
1E0F
Reserved
FORCE
ANALOG
OUTPUTS
1E10
Force Analog Outputs Function
---
---
---
F30
0 = Disabled
1E11
Force Analog Output 1
0 to 100
1
%
F1
0%
1E12
Force Analog Output 2
0 to 100
1
%
F1
0%
1E13
Force Analog Output 3
0 to 100
1
%
F1
0%
1E14
Force Analog Output 4
0 to 100
1
%
F1
0%
1E15
Force Analog Output 5
0 to 100
1
%
F1
0%
1E16
Force Analog Output 6
0 to 100
1
%
F1
0%
1E17
Force Analog Output 7
0 to 100
1
%
F1
0%
1E18
Reserved
↓
↓
↓
↓
↓
↓
↓
1E1F
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 22 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT