GE Multilin
745 Transformer Management Relay
6-19
6 ACTUAL VALUES
6.6 TARGET AND FLASH MESSAGES
6
The recorded event displayed for Logic inputs and Virtual Inputs will show the programmed name of the input/output. An
active target display may also be generated as a result of a self-test error. When this occurs, the target message will look
like this:
The
<ERROR>
part in the above display will be one of the following:
For more detail about these errors, refer to the next section. As well, there is an additional message that may appear as a
target message. It looks like this:
This message will be placed in the target message queue whenever
S1 745 SETUP
ÖØ
INSTALLATION
Ö
745 SETPOINTS
is set
to “Not Programmed”. This serves as a warning that the relay has not been programmed for the installation and is therefore
not in the in-service state.
6.6.2 SELF-TEST ERRORS
The 745 performs self-diagnostics at initialization (after power-up), and continuously thereafter (in a background task). The
tests ensure that every testable unit of the hardware is functioning correctly.
ANY SELF-TEST ERROR INDICATES A SERIOUS PROBLEM REQUIRING SERVICE.
MAJOR SELF-TEST ERRORS:
Upon detection of a major self-test error, the 745:
•
disables all protection functionality
•
turns on the front panel Self-Test Error LED
•
turns off the front panel In Service LED
•
de-energizes all output relays, including the Self-Test Relay
•
indicates the failure by inserting an appropriate message in the target message queue
•
records the failure in the Event Recorder
MINOR SELF-TEST ERRORS:
Upon detection of a minor self-test error, the 745:
•
turns on the front panel Self-Test Error LED
•
de-energizes the Self-Test Relay
•
indicates the failure by inserting an appropriate message in the target message queue
•
records the failure in the Event Recorder
SELF-TEST ERROR:
<ERROR>
Logic Power Out
Analog Output
Emulation Software
Real-Time Clock
Bad Xfmr Settings
Flexlogic Eqn
DSP Processor
EEPROM Memory
Access Denied
Not Calibrated
Int Temperature
IRIG-B Signal
SETPOINTS HAVE NOT
BEEN PROGRAMMED!
CAUTION