5-90
745 Transformer Management Relay
GE Multilin
5.7 S5 OUTPUTS
5 SETPOINTS
5
This ordering of parameters of an equation, where the gate (or “operator”) follows the input (or “value”) is commonly
referred to as “Postfix” or “Reverse Polish” notation.
Figure 5–44: FLEXLOGIC™ EXAMPLE IMPLEMENTED
Any equation entered in the 745 that does not make logical sense according to the notation described here, will be flagged
as a self-test error. The
SELF TEST ERROR: FlexLogic Eqn
message will be displayed until the error is corrected.
5.7.4 OUTPUT RELAYS
PATH: SETPOINTS
ÖØ
S5 OUTPUTS
Ö
OUTPUT RELAYS
Ö
OUTPUT RELAY 1(8)
This section contains the settings (including the FlexLogic™ equation) to configure output relays 1 to 8.
•
OUTPUT 1(8) NAME
: Press
edit the name of the output. The text may be changed from
Solid State Trip
one
character at a time, using the
and
keys. Press
to store the edit and advance to the next
character position.
•
OUTPUT 1(8) OPERATION
: Select "Latched" to maintain the Output 1(8) contacts in the energized state, even after
the condition that caused the contacts to operate is cleared, until a reset command is issued (or automatically after one
week). Select "Self-reset" to automatically de-energize the contacts after the condition is cleared. The solid state out-
put (Output 1) remains closed until externally reset by a momentary interruption of current, unless wired in parallel with
an electromechanical relay (Outputs 2 to 8) in which case it turns off when the relay operates.
OUTPUT RELAY 1
[ENTER] for more
OUTPUT 1 NAME:
Solid State Trip
Range: Enabled, Disabled
OUTPUT 1 OPERATION:
Self-Resetting
Range: Self-Resetting, Latched
OUTPUT 1 TYPE:
Trip
Range: Trip, Alarm, Control
OUTPUT 1 FLEXLOGIC
01: Percent Diff Op
Range: any FlexLogic™ input or gate
↓
OUTPUT 1 FLEXLOGIC
20: END
Range: any FlexLogic™ input or gate
OUTPUT 2 FLEXLOGIC
O1: Percent Diff OP
OUTPUT 2 FLEXLOGIC
O2: Inst Diff OP
OUTPUT 2 FLEXLOGIC
O3: Virtual Output 1
OUTPUT 2 FLEXLOGIC
O4: Logic Input 1
OUTPUT 2 FLEXLOGIC
O7: NOT
OUTPUT 2 FLEXLOGIC
O5: XOR (2 inputs)
XOR
AND
OR
OUTPUT 2 FLEXLOGIC
O8: Output Relay 2
OUTPUT 2 FLEXLOGIC
O6: Logic Input 2
OUTPUT 2 FLEXLOGIC
O9: AND (2 inputs)
OUTPUT 2 FLEXLOGIC
11: END
Output Relay 2
OPERATE
OUTPUT 2 FLEXLOGIC
1O: OR (4 inputs)
OUTPUT 2 FLEXLOGIC
20: END
...
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
VALUE
VALUE
ENTER