GE Multilin
745 Transformer Management Relay
7-53
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
F45
con’t
0000 0000 0010 0011
35 = W3 øC Demand
0000 0000 0010 0100
36 = Analog Input
0000 0000 0010 0101
37 = Max Event W1 Ia
0000 0000 0010 0110
38 = Max Event W1 Ib
0000 0000 0010 0111
39 = Max Event W1 Ic
0000 0000 0010 1000
40 = Max Event W1 Ig
0000 0000 0010 1001
41 = Max Event W2 Ia
0000 0000 0010 1010
42 = Max Event W2 Ib
0000 0000 0010 1011
43 = Max Event W2 Ic
0000 0000 0010 1100
44 = Max Event W2 Ig
0000 0000 0010 1101
45 = Max Event W3 Ia
0000 0000 0010 1110
46 = Max Event W3 Ib
0000 0000 0010 1111
47 = Max Event W3 Ic
0000 0000 0011 0000
48 = Max Event W3 Ig
F46
16 bits
TARGET TYPES
0000 0000 0000 0000
0 = Self-reset
0000 0000 0000 0001
1 = Latched
0000 0000 0000 0010
2 = None
F47
16 bits
FLEXLOGIC EQUATION
0000 0000 0000 0000
Token = END
0000 0001 0000 0000
Token = OFF
0000 0010 0000 0000
Token = ON
0000 0011 0000 0000
Token = NOT gate
0000 0100 xxxx xxxx
Token = OR gate
0000 0010
2 = 2 input OR gate
0000 0011
3 = 3 input OR gate
↓
↓
0001 0011
19 = 19 input OR gate
0000 0101 xxxx xxxx
Token = AND gate
0000 0010
2 = 2 input AND gate
0000 0011
3 = 3 input AND gate
↓
↓
0001 0011
19 = 19 input AND gate
0000 0110 xxxx xxxx
Token = NOR gate
0000 0010
2 = 2 input NOR gate
0000 0011
3 = 3 input NOR gate
↓
↓
0001 0011
19 = 19 input NOR gate
0000 0111 xxxx xxxx
Token = NAND gate
0000 0010
2 = 2 input NAND gate
0000 0011
3 = 3 input NAND gate
↓
↓
0001 0011
19 = 19 input NAND gate
0000 1000 xxxx xxxx
Token = XOR gate
0000 0010
2 = 2 input XOR gate
0000 0011
3 = 3 input XOR gate
↓
↓
0001 0011
19 = 19 input XOR gate
0000 1001 xxxx xxxx
Token = Element Pickup
0000 0000
0= Any Element
0000 0001
1 = Any W1 Overcurrent
0000 0010
2 = Any W2 Overcurrent
0000 0011
3 = Any W3 Overcurrent
0000 0100
4 = Percent Differential
0000 0101
5 = Inst Differential
0000 0110
6 = Winding 1 Phase Time O/C
Table 7–6: 745 DATA FORMATS (Sheet 11 of 25)
CODE
APPLICABLE BITS
DEFINITION
F47
con’t
0000 0111
7 = Winding 2 Phase Time O/C
0000 1000
8 = Winding 3 Phase Time O/C
0000 1001
9 = Winding 1 Phase Inst O/C 1
0000 1010
10 = Winding 2 Phase Inst O/C 1
0000 1011
11 = Winding 3 Phase Inst O/C 1
0000 1100
12 = Winding 1 Phase Inst O/C 2
0000 1101
13 = Winding 2 Phase Inst O/C 2
0000 1110
14 = Winding 3 Phase Inst O/C 2
0000 1111
15 = Winding 1 Neutral Time O/C
0001 0000
16 = Winding 2 Neutral Time O/C
0001 0001
17 = Winding 3 Neutral Time O/C
0001 0010
18 = Winding 1 Neutral Inst O/C 1
0001 0011
19 = Winding 2 Neutral Inst O/C 1
0001 0100
20 = Winding 3 Neutral Inst O/C 1
0001 0101
21 = Winding 1 Neutral Inst O/C 2
0001 0110
22 = Winding 2 Neutral Inst O/C 2
0001 0111
23 = Winding 3 Neutral Inst O/C 2
0001 1000
24 = Winding 1 Ground Time O/C
0001 1001
25 = Winding 2 Ground Time O/C
0001 1010
26 = Winding 3 Ground Time O/C
0001 1011
27 = Winding 1 Ground Inst O/C 1
0001 1100
28 = Winding 2 Ground Inst O/C 1
0001 1101
29 = Winding 3 Ground Inst O/C 1
0001 1110
30 = Winding 1 Ground Inst O/C 2
0001 1111
31 = Winding 2 Ground Inst O/C 2
0010 0000
32 = Winding 3 Ground Inst O/C 2
0010 0001
33=Winding 1 Restricted Gnd Fault
0010 0010
34=Winding 2 Restricted Gnd Fault
0010 0011
35=Winding 3 Restricted Gnd Fault
0010 0100
36=Winding 1 Restricted Gnd Trend
0010 0101
37=Winding 2 Restricted Gnd Trend
0010 0110
38=Winding 3 Restricted Gnd Trend
0010 0111
39 = Winding 1 Neg. Seq. Time O/C
0010 1000
40 = Winding 2 Neg. Seq. Time O/C
0010 1001
41 = Winding 3 Neg. Seq. Time O/C
0010 1010
42 = Winding 1 Neg. Seq. Inst O/C
0010 1011
43 = Winding 2 Neg. Seq. Inst O/C
0010 1100
44 = Winding 3 Neg. Seq. Inst O/C
0010 1101
45 = Underfrequency 1
0010 1110
46 = Underfrequency 2
0010 1111
47 = Frequency Decay Rate 1
0011 0000
48 = Frequency Decay Rate 2
0011 0001
49 = Frequency Decay Rate 3
0011 0010
50 = Frequency Decay Rate 4
0011 0011
51 = Overfrequency
0011 0100
52 = 5th Harmonic Level
0011 0101
53 = Volts-Per-Hertz 1
0011 0110
54 = Volts-Per-Hertz 2
0011 0111
55 = Winding 1 THD Level
0011 1000
56 = Winding 2 THD Level
0011 1001
57 = Winding 3 THD Level
0011 1010
58 = Winding 1 Harmonic Derating
0011 1011
59 = Winding 2 Harmonic Derating
0011 1100
60 = Winding 3 Harmonic Derating
0011 1101
61 = Hottest-Spot Temperature Limit
0011 1110
62 = Loss-Of-Life Limit
Table 7–6: 745 DATA FORMATS (Sheet 12 of 25)
CODE
APPLICABLE BITS
DEFINITION