GE Multilin
745 Transformer Management Relay
7-59
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
F88
con’t
0000 0000 0000 0111
7 = Logic Input 7
0000 0000 0000 1000
8 = Logic Input 8
0000 0000 0000 1001
9 = Logic Input 9
0000 0000 0000 1010
10 = Logic Input 10
0000 0000 0000 1011
11 = Logic Input 11
0000 0000 0000 1100
12 = Logic Input 12
0000 0000 0000 1101
13 = Logic Input 13
0000 0000 0000 1110
14 = Logic Input 14
0000 0000 0000 1111
15 = Logic Input 15
0000 0000 0001 0000
16 = Logic Input 16
F89
16 bits
LOW VOLTAGE WINDING RATING
0000 0000 0000 0000
0 = Above 5 kV
0000 0000 0000 0001
1 = 1 kV to 5 kV
0000 0000 0000 0010
2 = Below 1 kV
F90
16 bits
UNSIGNED VALUE
AUTORANGING VOLTAGE / RATED
LOAD / MIN TAP VOLTAGE
For LOW VOLTAGE WINDING RATING
≥
5 kV
Format: Unsigned value, 1 decimal place
Example: 123.4 stored as 1234
For 1 kV
≤
LOW VOLTAGE WINDING RATING < 5 kV
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For LOW VOLTAGE WINDING RATING < 1 kV
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234
F91
16 bits
UNSIGNED VALUE, AUTORANGING
VOLTAGE INCREMENT PER TAP
For LOW VOLTAGE WINDING RATING
≥
Above 5 kV
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For 1 kV
≤
LOW VOLTAGE WINDING RATING < 5 kV
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234
For LOW VOLTAGE WINDING RATING < 1 kV
Format: Unsigned value, 4 decimal places
Example: 0.1234 stored as 1234
F92
16 bits
HARMONIC NUMBER
0000 0000 0000 0010
0 = 2nd
0000 0000 0000 0011
1 = 3rd
0000 0000 0000 0100
2 = 4th
0000 0000 0000 0101
3 = 5th
0000 0000 0000 0110
4 = 6th
0000 0000 0000 0111
5 = 7th
0000 0000 0000 1000
6 = 8th
0000 0000 0000 1001
7 = 9th
0000 0000 0000 1010
8 = 10th
0000 0000 0000 1011
9 = 11th
0000 0000 0000 1100
10 = 12th
0000 0000 0000 1101
11 = 13th
0000 0000 0000 1110
12 = 14th
0000 0000 0000 1111
13 = 15th
0000 0000 0001 0000
14 = 16th
0000 0000 0001 0001
15 = 17th
0000 0000 0001 0010
16 = 18th
0000 0000 0001 0011
17 = 19th
0000 0000 0001 0100
18 = 20th
0000 0000 0001 0101
19 = 21st
Table 7–6: 745 DATA FORMATS (Sheet 23 of 25)
CODE
APPLICABLE BITS
DEFINITION
F93
16 bits
SIGNED VALUE
AUTORANGING BASED ON
WINDING 1 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A
<
CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F94
16 bits
SIGNED VALUE
AUTORANGING BASED ON
WINDING 2 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F95
16 bits
SIGNED VALUE
AUTORANGING BASED ON
WINDING 3 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
F96
32 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 1 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Signed value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Signed value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Signed value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Signed value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Signed value, scaled by 10
Example: 12340 stored as 1234
Table 7–6: 745 DATA FORMATS (Sheet 24 of 25)