GE Multilin
745 Transformer Management Relay
7-57
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
F70
16 bits
TRACE/PLAYBACK MEMORY DATA
Trace/Playback Channel Selector Index = 0 to 10
(i.e. any current input)
2'S COMPLEMENT SIGNED VALUE
Example: 1.000 x CT stored as 500; -0.500 x CT stored as -250
Trace/Playback Channel Selector Index = 11 (i.e. Voltage)
2'S COMPLEMENT SIGNED VALUE
Example: 1.000 x VT stored as 1000; -0.500 x VT stored as -500
Trace Channel Selector Index = 12 (i.e. Logic Inputs)
AS PER FORMAT F49
Example: "Logic Inputs 1 and 3 closed" stored as 0005 hex
Trace Channel Selector Index = 13 (i.e. Output Relays)
AS PER FORMAT F50
Example: "Output Relays 2 and 4 energized" stored as 000Ah
F71
16 bits
FACTORY SERVICE COMMANDS
0000 0000 0000 0000
0 = Clear Any Pending Commands
0000 0000 0000 0001
1 = Load Factory Default Setpoints
0000 0000 0000 0010
2 = Load Default Calibration Data
0000 0000 0000 0011
3 = Clear Diagnostic Data
0000 0000 0000 0100
4 = Clear RMS Min/Max Data
F72
16 bits
FORCE OTHER HARDWARE
xxxx xxxx xxxx xxx1
LEDs (0=Normal, 1= Use LED force
codes)
xxxx xxxx xxxx xx1x
Not Used
xxxx xxxx xxxx x1xx
External Watchdog
(0=Normal, 1=Stop Updating)
xxxx xxxx xxxx 1xxx
Internal Watchdog
(0=Normal, 1=Stop Updating)
F73
16 bits
PARITY
0000 0000 0000 0000
0 = None
0000 0000 0000 0001
1 = Odd
0000 0000 0000 0010
2 = Even
F74
16 bits
EDIT SETPOINT GROUP
0000 0000 0000 0000
0 = Group 1
0000 0000 0000 0001
1 = Group 2
0000 0000 0000 0010
2 = Group 3
0000 0000 0000 0011
3 = Group 4
0000 0000 0000 0100
4 = Active Group
F75
16 bits
VIRTUAL INPUT PROGRAMMED
STATE
0000 0000 0000 0000
0 = Open
0000 0000 0000 0001
1 = Closed
F76
16 bits
FLEXLOGIC EQUATION ERROR
0000 0000 0000 0000
0 = None
0000 0000 0000 0001
1 = Output Relay 1
0000 0000 0000 0010
2 = Output Relay 2
0000 0000 0000 0011
3 = Output Relay 3
0000 0000 0000 0100
4 = Output Relay 4
0000 0000 0000 0101
5 = Output Relay 5
0000 0000 0000 0110
6 = Output Relay 6
0000 0000 0000 0111
7 = Output Relay 7
0000 0000 0000 1000
8 = Output Relay 8
0000 0000 0000 1001
9 = Trace Memory Trigger
0000 0000 0000 1010
10 = Virtual Output 1
0000 0000 0000 1011
11 = Virtual Output 2
0000 0000 0000 1100
12 = Virtual Output 3
0000 0000 0000 1101
13 = Virtual Output 4
0000 0000 0000 1110
14 = Virtual Output 5
Table 7–6: 745 DATA FORMATS (Sheet 19 of 25)
CODE
APPLICABLE BITS
DEFINITION
F77
16 bits
BAD TRANSFORMER SETTINGS
ERROR
0000 0000 0000 0000
0 = None
0000 0000 0000 0001
1 = W1-W2 Ratio Mismatch
0000 0000 0000 0010
2 = W1-W3 Ratio Mismatch
0000 0000 0000 0011
3 = Load Loss
0000 0000 0000 0100
4 = W1 Eddy-Current Loss
0000 0000 0000 0101
5 = W2 Eddy-Current Loss
0000 0000 0000 0110
6 = W3 Eddy-Current Loss
0000 0000 0000 0111
7 = W1 Rated Load
0000 0000 0000 1000
8 = W2 Rated Load
0000 0000 0000 1001
9 = W3 Rated Load
F78
16 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 1 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Unsigned value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Unsigned value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Unsigned value, scaled by 10
Example: 12340 stored as 1234
F79
16 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 2 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Unsigned value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Unsigned value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Unsigned value, scaled by 10
Example: 12340 stored as 1234
F80
16 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 3 PHASE CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Unsigned value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Unsigned value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Unsigned value, scaled by 10
Example: 12340 stored as 1234
Table 7–6: 745 DATA FORMATS (Sheet 20 of 25)
CODE
APPLICABLE BITS
DEFINITION