7-42
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
WINDING 3
NEG SEQ TIME
O/C
2270
Winding 3 Neg Seq Time O/C Function
---
---
---
F30
0 = Disabled
2271
Winding 3 Neg Seq Time O/C Target
---
---
---
F46
1 = Latched
2272
Winding 3 Neg Seq Time O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
25 = 0.25
×
CT
2273
Winding 3 Neg Seq Time O/C Shape
---
---
---
F36
0 = Ext Inverse
2274
Winding 3 Neg Seq Time O/C Multiplier
0.00 to 100.00
0.01
---
F3
100 = 1.00
2275
Winding 3 Neg Seq Time O/C Reset
---
---
---
F68
1 = Linear
2276
Winding 3 Neg Seq Time O/C Block
---
---
---
F87
0 = Disabled
2277
Reserved
↓
↓
↓
↓
↓
↓
↓
227F
Reserved
WINDING 1
NEG SEQ INST
O/C
2280
Winding 1 Neg Seq Inst O/C Function
---
---
---
F30
0 = Disabled
2281
Winding 1 Neg Seq Inst O/C Target
---
---
---
F46
1 = Latched
2282
Winding 1 Neg Seq Inst O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2283
Winding 1 Neg Seq Inst O/C Delay
0 to 60000
1
ms
F1
0 ms
2284
Winding 1 Neg Seq Inst O/C Block
---
---
---
F87
0 = Disabled
2285
Reserved
↓
↓
↓
↓
↓
↓
↓
228F
Reserved
WINDING 2
NEG SEQ INST
O/C
2290
Winding 2 Neg Seq Inst O/C Function
---
---
---
F30
0 = Disabled
2291
Winding 2 Neg Seq Inst O/C Target
---
---
---
F46
1 = Latched
2292
Winding 2 Neg Seq Inst O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
2293
Winding 2 Neg Seq Inst O/C Delay
0 to 60000
1
ms
F1
0 ms
2294
Winding 2 Neg Seq Inst O/C Block
---
---
---
F87
0 = Disabled
2295
Reserved
↓
↓
↓
↓
↓
↓
↓
229F
Reserved
WINDING 3
NEG SEQ INST
O/C
22A0
Winding 3 Neg Seq Inst O/C Function
---
---
---
F30
0 = Disabled
22A1
Winding 3 Neg Seq Inst O/C Target
---
---
---
F46
1 = Latched
22A2
Winding 3 Neg Seq Inst O/C Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
22A3
Winding 3 Neg Seq Inst O/C Delay
0 to 60000
1
ms
F1
0 ms
22A4
Winding 3 Neg Seq Inst O/C Block
---
---
---
F87
0 = Disabled
UNDER
FREQUENCY
1
22A5
Reserved
↓
↓
↓
↓
↓
↓
↓
22AF
Reserved
22B0
Underfrequency 1 Function
---
---
---
F30
0 = Disabled
22B1
Underfrequency 1 Target
---
---
---
F46
0 = Self-reset
22B2
Underfrequency 1 Minimum Operating Current
0.05 to 1.00
0.01
×
CT
F3
20 = 0.20
×
CT
22B3
Underfrequency 1 Pickup
45.00 to 59.99
0.01
Hz
F3
5900 = 59.0 Hz
22B4
Underfrequency 1 Delay
0.00 to 600.00
0.01
s
F3
100 = 1.00 s
22B5
Underfrequency 1 Block
---
---
---
F87
0 = Disabled
22B6
Underfrequency 1 Current Sensing
---
---
---
F30
1 = Enabled
22B7
Underfrequency 1 Minimum Operating Voltage
0.10 to 0.99
0.01
×
VT
F3
50 = 0.50
×
VT
22B8
Reserved
↓
↓
↓
↓
↓
↓
↓
22BF
Reserved
UNDER
FREQUENCY
2
22C0
Underfrequency 2 Function
---
---
---
F30
0 = Disabled
22C1
Underfrequency 2 Target
---
---
---
F46
1 = Latched
22C2
Underfrequency 2 Minimum Operating Current
0.05 to 1.00
0.01
×
CT
F3
20 = 0.20
×
CT
22C3
Underfrequency 2 Pickup
45.00 to 59.99
0.01
Hz
F3
5880 = 58.8 Hz
22C4
Underfrequency 2 Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
22C5
Underfrequency 2 Block
---
---
---
F87
0 = Disabled
22C6
Underfrequency 2 Current Sensing
---
---
---
F30
1 = Enabled
22C7
Underfrequency 2 Minimum Operating Voltage
0.01 to 0.99
0.01
×
VT
F3
50 = 0.50
×
VT
Table 7–5: 745 MEMORY MAP (Sheet 30 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT