GE Multilin
745 Transformer Management Relay
5-97
5 SETPOINTS
5.8 S6 TESTING
5
•
W1(W3) PHASE A(C) CURRENT MAGNITUDE
: Enter the Winding 1(3) Phase A(C) current magnitude (in terms of
the winding full load current) while in Fault Mode.
•
W1(3) PHASE A(C) CURRENT ANGLE
: Enter the Winding 1(3) Phase A(C) current angle (with respect to the Winding
1 Phase A current phasor) while in Fault Mode. Note that the Winding 1 Phase A current angle cannot be edited and is
used as a reference for the other phase angles.
•
W1(3) GROUND CURRENT MAGNITUDE
: Enter the Winding 1(3) Ground Current magnitude (in terms of the winding
FLC) while in Fault Mode. Note that ground refers to the measured CT current in the connection between transformer
neutral and ground. As such, this message only appears for wye or zig-zag connected windings.
•
W1(3) GROUND CURRENT ANGLE
: Enter the Winding 1(3) ground current angle (with respect to the Winding 1
Phase A current phasor). This message only appears for wye or zig-zag connected windings.
W2 PHASE B CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
W3 PHASE B CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
W1 PHASE C CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
W2 PHASE C CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
W3 PHASE C CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
W1 GROUND CURRENT
MAGNITUDE: 1.0 x CT
Range: 0.0 to 40.0 x CT in steps of 0.1
W2 GROUND CURRENT
MAGNITUDE: 1.0 x CT
Range: 0.0 to 40.0 x CT in steps of 0.1
W3 GROUND CURRENT
MAGNITUDE: 1.0 x CT
Range: 0.0 to 40.0 x CT in steps of 0.1
W1 GROUND CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
W2 GROUND CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
W3 GROUND CURRENT
ANGLE: 0°
Range: 0 to 359° in steps of 1
VOLTAGE INPUT
MAGNITUDE: 1.0 x VT
Range: 0.0 to 2.0 x VT in steps of 0.1
VOLTAGE INPUT
ANGLE: 0° Lag
Range: 0 to 359° Lag in steps of 1
FREQUENCY:
60.00 Hz
Range: 45.00 to 60.00 Hz in steps of 0.01
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Содержание TRANSFORMER MANAGEMENT RELAY 745
Страница 2: ...Courtesy of NationalSwitchgear com ...