7-46
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
WINDING 3
CURRENT
DEMAND
23D4
Reserved
↓
↓
↓
↓
↓
↓
↓
23DF
Reserved
23E0
Winding 3 Current Demand Function
---
---
---
F30
0 = Disabled
23E1
Winding 3 Current Demand Target
---
---
---
F46
0 = Self-reset
23E2
Winding 3 Current Demand Pickup
---
---
A
F80
400 A
23E3
Winding 3 Current Demand Block
---
---
---
F87
0 = Disabled
23E4
Reserved
↓
↓
↓
↓
↓
↓
↓
23EF
Reserved
XFORMER
OVERLOAD
23F0
Transformer Overload Function
---
---
---
F30
0 = Disabled
23F1
Transformer Overload Target
---
---
---
F46
0 = Self-reset
23F2
Transformer Overload Pickup
50 to 300
1
% rated
F1
208% rated
23F3
Transformer Overload Delay
0 to 60000
1
s
F1
10 s
23F4
Transformer Overload Block
---
---
---
F87
0 = Disabled
23F5
Transformer Overtemperature Alarm Signal
---
---
---
F88
0 = Disabled
23F6
Reserved
↓
↓
↓
↓
↓
↓
↓
23FF
Reserved
AGING
FACTOR
LIMIT
2400
Aging Factor Limit Function
---
---
---
F30
0 = Disabled
2401
Aging Factor Limit Target
---
---
---
F46
0 = Self-reset
2402
Aging Factor Limit Pickup
1.1 to 10.0
0.1
--
F2
20 = 2.0
2403
Aging Factor Limit Delay
0 to 60000
1
minutes
F1
10 minutes
2404
Aging Factor Limit Block
---
---
---
F87
0 = Disabled
2405
Reserved
↓
↓
↓
↓
↓
↓
↓
240F
Reserved
TAP CHANGER
FAILURE
2410
Tap Changer Failure Function
---
---
---
F30
0 = Disabled
2411
Tap Changer Failure Target
---
---
---
F46
0 = Self-reset
2412
Tap Changer Failure Delay
0 to 600.00
0.01
s
F3
500 = 5.00 s
2413
Tap Changer Failure Block
---
---
---
F87
0 = Disabled
2414
Reserved
↓
↓
↓
↓
↓
↓
↓
3FFF
Reserved
Trace Memory (Addresses 4000 to 47FF) - Read Only
TRACE
MEMORY
4000
Trace Memory Last Clear Date (2 registers)
---
---
---
F23
---
4002
Trace Memory Last Clear Time (2 registers)
---
---
---
F22
---
4004
Total Number of Trace Triggers Since Last Clear
0 to 65535
1
---
F1
---
4005
Trace Buffer Selector Index (XX) [read/write]
1 to 65535
1
---
F1
---
4006
Trace Channel Selector Index (YY) [read/write]
---
---
---
F65
---
4007
Reserved
↓
↓
↓
↓
↓
↓
↓
400F
Reserved
4010
Trace Buffer XX Trigger Date (2 registers)
---
---
---
F23
---
4012
Trace Buffer XX Trigger Time (2 registers)
---
---
---
F22
---
4014
Trace Buffer XX Trigger Cause
---
---
---
F85
---
4015
Trace Buffer XX Trigger Sample Index
0 to 1023
1
---
F1
---
4016
Trace Buffer XX System Frequency
2.00 to 65.00
0.01
Hz
F3
---
4017
Trace Buffer XX Channel YY Sample 0
---
---
---
F70
---
4018
Trace Buffer XX Channel YY Sample 1
---
---
---
F70
---
↓
↓
↓
↓
↓
↓
↓
4416
Trace Buffer XX Channel YY Sample 1023
---
---
---
F70
---
4417
Reserved
↓
↓
↓
↓
↓
↓
↓
47FF
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 34 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Содержание TRANSFORMER MANAGEMENT RELAY 745