GE Multilin
745 Transformer Management Relay
5-61
5 SETPOINTS
5.6 S4 ELEMENTS
5
c) GROUND INSTANTANEOUS OVERCURRENT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
NEUTRAL OC
ÖØ
W1(3) NTRL INST OC 1(2)
•
W1(3) GROUND INST OC 1(2) PICKUP
: Enter the level of ground current (in units of relay nominal current) above
which the Winding 1(3) Ground Instantaneous Overcurrent 1 element will pickup and start the delay timer.
•
W1(3) GROUND INST OC 1(2) DELAY
: Enter the time that the ground current must remain above the pickup level
before the element operates.
The messages
above and scheme logic below are identical for Windings 2 and 3 of Ground Instantaneous
Overcurrent 1 and all windings on the Ground Instantaneous Overcurrent 2 element.
Figure 5–20: GROUND IOC 1 SCHEME LOGIC
W1 GND INST OC 1
[ENTER] for more
W1 GROUND INST OC 1
FUNCTION: Disabled
Range: Enabled, Disabled
W1 GROUND INST OC 1
TARGET: Latched
Range: Self-Reset, Latched, None
W1 GROUND INST OC 1
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 x CT in steps of 0.01
W1 GROUND INST OC 1
DELAY: 0 ms
Range: 0 to 60000 ms in steps of 1
W1 GROUND INST OC 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
NOTE