5-70
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
c) FREQUENCY DECAY
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
FREQUENCY
ÖØ
FREQUENCY DECAY
•
MINIMUM OPERATING CURRENT
: Enter the minimum value of Winding 1 Phase A current (in units of relay nominal
current) required to allow the frequency decay element to operate.
•
MINIMUM OPERATING VOLTAGE
: Enter the minimum value of voltage (in units of relay nominal voltage) required to
allow the underfrequency element to operate.
•
FREQUENCY DECAY THRESHOLD
: Enter the frequency (in Hz) below which the four frequency rate-of-change lev-
els of the frequency decay element will be allowed to operate.
•
FREQUENCY DECAY RATE 1(4)
: Enter the rate of frequency decay beyond which the corresponding element oper-
ates.
FREQUENCY DECAY
[ENTER] for more
FREQUENCY DECAY
FUNCTION: Disabled
Range: Enabled, Disabled
FREQUENCY DECAY
TARGET: Self-Reset
Range: Self-Reset, Latched, None
CURRENT SENSING:
Enabled
Range: Enabled, Disabled
MINIMUM OPERATING
CURRENT: 0.20 x CT
Range: 0.20 to 1.00 x CT in steps of 0.01
MINIMUM OPERATING
VOLTAGE: 0.50 x VT
Range: 0.10 to 0.99 x CT in steps of 0.01
FREQUENCY DECAY
THRESHOLD: 59.50 Hz
Range: 45.00 to 59.99 Hz in steps of 0.01
FREQUENCY DECAY
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
FREQUENCY DECAY
RATE 1: 0.4 Hz/s
Range: 0.1 to 5.0 Hz/s in steps of 0.1
FREQUENCY DECAY
RATE 2: 1.0 Hz/s
Range: 0.1 to 5.0 Hz/s in steps of 0.1
FREQUENCY DECAY
RATE 3: 2.0 Hz/s
Range: 0.1 to 5.0 Hz/s in steps of 0.1
FREQUENCY DECAY
RATE 4: 4.0 Hz/s
Range: 0.1 to 5.0 Hz/s in steps of 0.1
FREQUENCY DECAY
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE