GE Multilin
745 Transformer Management Relay
7-35
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
SIMULATION
SETUP
1E20
Simulation Function
---
---
---
F48
0 = Disabled
1E21
Block Operation of Outputs
---
---
---
F67
255 = 12345678
1E22
Start Fault Mode Signal
---
---
---
F88
0 = Disabled
1E23
Start Playback Mode Signal
---
---
---
F88
0 = Disabled
1E24
Reserved
↓
↓
↓
↓
↓
↓
↓
1E27
Reserved
SIMULATION
PREFAULT
VALUES
1E28
Prefault Wdg 1 Phase ABC Current Magnitudes
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E29
Prefault Wdg 2 Phase ABC Current Magnitudes
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E2A
Prefault Wdg 3 Phase ABC Current Magnitudes
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E2B
Prefault Voltage Input Magnitude
0.0 to 2.0
0.1
×
VT
F2
10 = 1.0
×
VT
1E2C
Reserved
↓
↓
↓
↓
↓
↓
↓
1E2F
Reserved
SIMULATION
FAULT VALUES
1E30
Fault Winding 1 Phase A Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E31
Fault Winding 1 Phase A Current Angle
---
---
°
F1
0°
1E32
Fault Winding 1 Phase B Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E33
Fault Winding 1 Phase B Current Angle
0 to 359
1
° Lag
F1
120° Lag
1E34
Fault Winding 1 Phase C Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E35
Fault Winding 1 Phase C Current Angle
0 to 359
1
° Lag
F1
240° Lag
1E36
Fault Winding 1 Ground Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
0.0 x CT
1E37
Fault Winding 1 Ground Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E38
Fault Winding 2 Phase A Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E39
Fault Winding 2 Phase A Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E3A
Fault Winding 2 Phase B Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E3B
Fault Winding 2 Phase B Current Angle
0 to 359
1
° Lag
F1
120° Lag
1E3C
Fault Winding 2 Phase C Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E3D
Fault Winding 2 Phase C Current Angle
0 to 359
1
° Lag
F1
240° Lag
1E3E
Fault Winding 2 Ground Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
0.0
×
CT
1E3F
Fault Winding 2 Ground Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E40
Fault Winding 3 Phase A Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E41
Fault Winding 3 Phase A Current Angle
0 to 359
1
° Lag
F1
330° Lag
1E42
Fault Winding 3 Phase B Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E43
Fault Winding 3 Phase B Current Angle
0 to 359
1
° Lag
F1
90° Lag
1E44
Fault Winding 3 Phase C Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
10 = 1.0
×
CT
1E45
Fault Winding 3 Phase C Current Angle
0 to 359
1
° Lag
F1
210° Lag
1E46
Fault Winding 3 Ground Current Magnitude
0.0 to 40.0
0.1
×
CT
F2
0.0
×
CT
1E47
Fault Winding 3 Ground Current Angle
0 to 359
1
° Lag
F1
0° Lag
1E48
Fault Voltage Input Magnitude
0.0 to 2.0
0.1
×
VT
F2
10 = 1.0
×
VT
1E49
Fault Voltage Input Angle
0 to 359
1
° Lag
F1
0° Lag
1E4A
Fault Frequency
45.00 to 60.00
0.01
Hz
F3
60.00 Hz
1E4B
Reserved
↓
↓
↓
↓
↓
↓
↓
1FFF
Reserved
Setpoint Group 1/2/3/4 (Addresses 2000 to 3FFF) - Read / Write
PERCENT
DIFFERENTIAL
2000
Percent Differential Function
---
---
---
F30
1 = Enabled
2001
Percent Differential Target
---
---
---
F46
1 = Latched
2002
Percent Differential Pickup
0.05 to 1.00
0.01
×
CT
F3
30 = 0.30
×
CT
2003
Percent Differential Slope 1
15 to 100
1
%
F1
25%
2004
Percent Differential Break Point
1.0 to 20.0
0.1
×
CT
F2
20 = 2.0
×
CT
2005
Percent Differential Slope 2
50 to 100
1
%
F1
100%
2006
Percent Differential Block
---
---
---
F87
0 = Disabled
2007
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 23 of 35)