A
Signal programmed to digital output
B
DO1 or DO2 output
C
ON-delay
D
OFF-delay
10.227 (ID 489) Digital Output 2 Signal Selection
Location in the menu:
P2.3.2.1
(Multi-Purpose Control Application)
Use this parameter to connect the digital output signal to the digital output of your selection.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
).
10.224 (ID 486) Digital Output 1 Signal Selection
10.228 (ID 490) Digital Output 2 Function
Location in the menu:
P2.3.2.2
(Multi-Purpose Control Application)
Use this parameter to select the function for the digital output signal.
See
10.72 (ID 312) Digital Output Function
10.229 (ID 491) Digital Output 2 On-Delay
Location in the menu:
P2.3.2.3
(Multi-Purpose Control Application)
Use this parameter to set the ON delay for the digital output.
See
10.225 (ID 487) Digital Output 1 On-Delay
.
10.230 (ID 492) Digital Output 2 Off-Delay
Location in the menu:
P2.3.2.4
(Multi-Purpose Control Application)
Use this parameter to set the OFF delay for the digital output.
See
10.226 (ID 488) Digital Output 1 Off-Delay
.
10.231 (ID 493) Adjust Input
Location in the menu:
P2.2.1.4
(Multi-Purpose Control Application)
Use this parameter to select the signal that adjusts the frequency reference of the motor.
For selection 5 "Signal from fieldbus (FBProcessDataIN), see
10.624 Fieldbus Control Parameters (IDs 850–859)
G2.9
.
44 Hz
40 Hz
36 Hz
e3
0bh063.1
0
A
B
C
D
E
Illustration 67: An Example of Adjust Input
AB296635287482en-000301 / DPD00903 | 229
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide