Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.19
UP Zero frequency load
5.0
150.0
%
10.0
715
-
P2.7.20
Underload protection time limit
2.00
600.00
s
20.00
716
-
P2.7.21
Response to thermistor fault
0
3
-
2
732
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.22
Response to fieldbus fault
0
3
-
2
733
P2.7.23
Response to slot fault
0
3
-
2
734
3.4.9 Autorestart Parameters (Control Panel: Menu M2 -> G2.8)
Table 13: Autorestart Parameters, G2.8
Index
Parameter
Min
Max
Unit Default
ID
Description
P2.8.1
Wait time
0.10 10.00
s
0.50
717 -
P2.8.2
Trial time
0.00 60.00
s
30.00
718 -
P2.8.3
Start function
0
2
-
0
719 0 = Ramp
1 = Flying start
2 = According to P2.4.6
P2.8.4
Number of tries after undervoltage trip
0
10
-
0
720 -
P2.8.5
Number of tries after overvoltage trip
0
10
-
0
721 -
P2.8.6
Number of tries after overcurrent trip
0
3
-
0
722 -
P2.8.7
Number of tries after 4 mA reference trip
0
10
-
0
723 -
P2.8.8
Number of tries after motor temperature fault trip
0
10
-
0
726 -
P2.8.9
Number of tries after external fault trip
0
10
-
0
725 -
P2.8.10
Number of tries after underload fault trip
0
10
-
0
738 -
3.4.10 Keypad Control (Control Panel: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed in this table. See the
Keypad control
menu in
the User Manual of the product.
Table 14: Keypad Control Parameters, M3
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.1
Control place
1
3
-
1
125
1 = I/0 terminal
2 = Keypad
AB296635287482en-000301 / DPD00903 | 27
Danfoss A/S © 2023.02
Standard Application
VACON® NX All-in-One
Application Guide