10.632 Fieldbus Control in Detail
Combina-
tion
P7.x.1.4 Operate
Mode (Fieldbus op-
tion board)
P2.9.35 Fieldbus
State Machine
Note
1
ProfiDrive
Standard
See fieldbus option board manual. Control Word and Status
Word are explained there.
2
ByPass
ProfiDrive
10.632.1 Combination 2: Bypass - ProfiDrive
3
ByPass
Standard
10.632.2 Combination 3: Bypass - Standard
.
4
ProfiDrive
ProfiDrive
Drive cannot be operated from fieldbus when this combination
is activated.
10.632.1 Combination 2: Bypass - ProfiDrive
Table 126: Control Word (ProfiDrive)
Signal
Description
b0
ON
0>1 resets the Switch On Inhibit state and bring the drive to Ready Run. Always reset after fault,
Coast Stop (b1), and Quick Stop (b2).
b1
Coast Stop
0=Coast stop Active
1=Coast stop NOT active
b2
Quick Stop
0=Coast stop Active
1=Coast stop NOT active
b3
Start
Normal start command
0=Stop the drive
1=Start the drive
b4
Ramp Output to Zero
0=Force speed ramp output to zero
1=Release speed ramp output
b5
Ramp Hold
0=Hold speed ramp output
1=Release speed ramp
b6
Ramp Input to Zero
0=Force speed ramp input to zero
1=Release speed ramp input
b7
Fault Reset
0=No Action
1=Reset active faults
b8
Inching 1
Run the drive with defined constant speed
0=No Action
1=Run with constant speed
b9
Inching 2
Run the drive with defined constant speed
0=No Action
1=Run with constant speed
b10 Fieldbus Control Enable Activate Fieldbus control when P3.1 =3/Fieldbus
0=Fieldbus Control NOT active
AB296635287482en-000301 / DPD00903 | 321
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......