Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.14.11
Start-up torque
0
3
-
0
621
0 = Not used
1 = Torque memory
2 = Torque reference
3 = Start-up torque fwd/rev
P2.6.14.12
Start-up torque FWD
-300.0
300.0
%
0.0
633
-
P2.6.14.13
Start-up torque REV
-300.0
300.0
%
0.0
634
-
P2.6.14.15
Encoder filter time
0.0
100
ms
0.0
618
-
P2.6.14.17
Current control P gain
0.00
100.00
%
40.00
617
-
Identification parameter group 2.6.15
P2.6.15.1
Speed step
-50.0
50.0
-
0.0
1252
-
1
Parameter value can only be changed after the AC drive has been stopped.
4.4.8 Protections (Control Panel: Menu M2 -> G2.7)
Table 22: Protections, G2.7
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.1
Response to 4 mA reference fault
0
5
-
0
700
0 = No response
1 = Warning
2 = Previous Freq.
3 = Wrng+Preset- Freq 2.7.2
4 = Fault, stop acc. to 2.4.7
5 = Fault, stop by coasting
P2.7.2
4 mA reference fault frequency
0.00
P2.1.2
Hz
0.00
728
-
P2.7.3
Response to external fault
0
3
-
2
701
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.4
Input phase supervision
0
3
-
0
730
P2.7.5
Response to undervoltage fault
0
1
-
0
727
0 = Fault stored in history
1 = Fault not stored
P2.7.6
Output phase supervision
0
3
-
2
702
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.7
Earth fault protection
0
3
-
2
703
P2.7.8
Thermal protection of the motor
0
3
-
2
704
P2.7.9
Motor ambient temperature factor
-100.0
100.0
%
0.0
705
-
P2.7.10
Motor cooling factor at zero speed
0.0
150.0
%
40.0
706
-
AB296635287482en-000301 / DPD00903
42 | Danfoss A/S © 2023.02
Local/Remote Control Application
VACON® NX All-in-One
Application Guide