Index
Parameter
Min
Max
Unit
Default
ID
Description
2 = Programmable
3 = Linear with flux optim.
P2.6.4
(1)
Field weakening point
8.00
320.00
Hz
50.00
602
-
P2.6.5
(1)
Voltage at field weakening point
10.00
200.00
%
100.00
603
-
P2.6.6
(1)
U/f curve midpoint frequency
0.00
P2.6.4
Hz
50.00
604
-
P2.6.7
(1)
U/f curve midpoint voltage
0.00
100.00
%
100.00
605
-
P2.6.8
(1)
Output voltage at zero frequency
0.00
40.00
%
Varies
606
-
P2.6.9
Switching frequency
1.0
Varies
kHz
Varies
601
-
P2.6.10
Overvoltage controller
0
2
-
1
607
0 = Not used
1 = Used (no ramping)
2 = Used (ramping)
P2.6.11
Undervoltage controller
0
2
-
2
608
0 = Not used
1 = Used
2 = Used (ramping to zero)
P2.6.12
Load drooping
0.00
100.00
%
0.00
620
-
P2.6.13
Identification
0
2/5
-
0
631
0 = No action
1 = Identification w/o run
2 = Identification with run
Only VACON
®
NXP:
3 = Encoder ID run
4 = No action
5 = ID Run Failed
Closed Loop parameter group 2.6.14
P2.6.14.1
Magnetizing current
0.00
2 x I
H
A
0.00
612
-
P2.6.14.2
Speed control P gain
1
1000
-
30
613
-
P2.6.14.3
Speed control I time
0.0
3200.0
ms
30.0
614
-
P2.6.14.5
Acceleration compensation
0.00
300.00
s
0.00
626
-
P2.6.14.6
Slip adjust
0
500
%
100
619
-
P2.6.14.7
Magnetizing current at start
0.00
I
L
A
0.00
627
-
P2.6.14.8
Magnetizing time at start
0
60000
ms
0
628
-
P2.6.14.9
0-speed time at start
0
32000
ms
100
615
-
P2.6.14.10
0-speed time at stop
0
32000
ms
100
616
-
AB296635287482en-000301 / DPD00903 | 41
Danfoss A/S © 2023.02
Local/Remote Control Application
VACON® NX All-in-One
Application Guide