Index
Parameter
Min
Max
Unit Default ID
Description
2 = High limit supervision
P2.3.2.15 Analog input supervised value
0.00
100.00 %
0.00
374 -
Table 100: Analog Output 1 (Control Panel: Menu M2 -> G2.3.3)
Index
Parameter
Min
Max
Unit Default ID
Description
P2.3.3.1
(1)
Analog output 1 signal selec-
tion
0.1
E.10
-
A.1
464 -
P2.3.3.2
Analog output function
0
14
-
1
307 0 = Not used (20 mA / 10 V)
1 = Output freq. (0–f
max
)
2 = Freq. reference (0–f
max
)
3 = Motor speed (0–Motor nominal speed
4 = Motor current (0–I
nMotor
)
5 = Motor torque (0–T
nMotor
)
6 = Motor power (0–P
nMotor
)
7 = Motor voltage (0–U
nMotor
)
8 = DC-link volt (0–1000 V)
9 = PID controller ref. value
10 = PID contr. act.value 1
11 = PID contr. act.value 2
12 = PID contr. error value
13 = PID controller output
14 = PT100 temperature
P2.3.3.3
Analog output filter time
0.00
10.00
s
1.00
308 0 = No filtering
P2.3.3.4
Analog output inversion
0
1
-
0
309 0 = Not inverted
1 = Inverted
P2.3.3.5
Analog output minimum
0
1
-
0
310 0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.3.6
Analog output scale
10
1000
%
100
311 -
P2.3.3.7
Analog output offset
-100.00 100.00 %
0.00
375 -
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
Table 101: Analog Output 2 (Control Panel: Menu M2 -> G2.3.4)
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.3.6.1
(1)
Analog output 2 signal selection
0.1
E.10
-
0.1
471
-
P2.3.6.2
Analog output 2 function
0
14
-
4
472
See P2.3.3.2
P2.3.6.3
Analog output 2 filter time
0.00
10.00
s
1.00
473
0 = No filtering
P2.3.6.4
Analog output 2 inversion
0
1
-
0
474
0 = Not inverted
AB296635287482en-000301 / DPD00903
142 | Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......