8.4.10 Pump and Fan Control Parameters (Control Panel: Menu M2 -> G2.9)
Table 108: Pump and Fan Control Parameters, G2.9
Index
Parameter
Min
Max
Unit Default ID
Description
P2.9.1
Number of auxiliary drives
0
4
-
1
1001 -
P2.9.2
Start frequency, auxiliary drive 1
P2.9.3 320.00 Hz
51.00
1002 -
P2.9.3
Stop frequency, auxiliary drive 1
P2.1.1 P2.9.2
Hz
10.00
1003 -
P2.9.4
Start frequency, auxiliary drive 2
P2.9.5 320.00 Hz
51.00
1004 -
P2.9.5
Stop frequency, auxiliary drive 2
P2.1.1 P2.9.4
Hz
10.00
1005 -
P2.9.6
Start frequency, auxiliary drive 3
P2.9.7 320.00 Hz
51.00
1006 -
P2.9.7
Stop frequency, auxiliary drive 3
P2.1.1 P2.9.6
Hz
10.00
1007 -
P2.9.8
Start frequency, auxiliary drive 4
P2.9.9 320.00 Hz
51.00
1008 -
P2.9.9
Stop frequency, auxiliary drive 4
P2.1.1 P2.9.8
Hz
10.00
1009 -
P2.9.10 Start delay, auxiliary drives
0.0
300.0
s
4.0
1010 -
P2.9.11 Stop delay, auxiliary drives
0.0
300.0
s
2.0
1011 -
P2.9.12 Reference step, auxiliary drive 1
0.00
100.00 %
0.00
1012 -
P2.9.13 Reference step, auxiliary drive 2
0.00
100.00 %
0.00
1013 -
P2.9.14 Reference step, auxiliary drive 3
0.00
100.00 %
0.00
1014 -
P2.9.15 Reference step, auxiliary drive 4
0.00
100.00 %
0.00
1015 -
P2.9.16 PID controller bypass
0
1
-
0
1020 1 = PID contr. bypassed
P2.9.17 Analogue input selection for input pres-
sure measurement
0
5
-
0
1021 0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = Fieldbus signal (FBPro-
cessDataIN3)
P2.9.18 Input pressure high limit
0.0
100.0
%
30.0
1022 -
P2.9.19 Input pressure low limit
0.0
100.0
%
20.0
1023 -
P2.9.20 Output pressure drop
0.0
100.0
%
30.0
1024 -
P2.9.21 Frequency drop delay
0.0
300.0
s
0.0
1025 0 = No delay
300 = No frequency drop nor
increase
AB296635287482en-000301 / DPD00903
148 | Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide