Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.11
Motor thermal time constant
1
200
min
Varies
707
-
P2.7.12
Motor duty cycle
0
150
%
100
708
-
P2.7.13
Stall protection
0
3
-
0
709
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.14
Stall current
0.00
2 x I
H
A
I
H
710
-
P2.7.15
Stall time limit
1.00
120.00
s
15.00
711
-
P2.7.16
Stall frequency limit
1.0
P2.1.2
Hz
25.00
712
-
P2.7.17
Underload protection
0
3
-
0
713
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.18
UP From Torque
10.0
150.0
%
50.0
714
-
P2.7.19
UP Zero frequency load
5.0
150.0
%
10.0
715
-
P2.7.20
Underload protection time limit
2.00
600.00
s
20.00
716
-
P2.7.21
Response to thermistor fault
0
3
-
2
732
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.22
Response to fieldbus fault
0
3
-
2
733
P2.7.23
Response to slot fault
0
3
-
2
734
4.4.9 Autorestart Parameters (Control Panel: Menu M2 -> G2.8)
Table 23: Autorestart Parameters, G2.8
Index
Parameter
Min
Max
Unit Default
ID
Description
P2.8.1
Wait time
0.10 10.00
s
0.50
717 -
P2.8.2
Trial time
0.00 60.00
s
30.00
718 -
P2.8.3
Start function
0
2
-
0
719 0 = Ramp
1 = Flying start
2 = According to P2.4.6
P2.8.4
Number of tries after undervoltage trip
0
10
-
0
720 -
P2.8.5
Number of tries after overvoltage trip
0
10
-
0
721 -
P2.8.6
Number of tries after overcurrent trip
0
3
-
0
722 -
AB296635287482en-000301 / DPD00903 | 43
Danfoss A/S © 2023.02
Local/Remote Control Application
VACON® NX All-in-One
Application Guide